IOM-CA5/SA5

2

IV. PRINCIPLE OF OPERATION

1. Movement occurs as pressure variations register

on the diaphragm. The registering pressure is the
inlet, P1, or upstream pressure. The range spring
op pos es di a phragm movement. As inlet pressure
drops, the range spring pushes the di a phragm

V. STARTUP

1 Start with the block valves closed.

2. Relax the range spring by turning the ad just ing

screw (1) CCW (viewed from above) a minimum
of three (3) full rev o lu tions. This reduces the inlet
(upstream) pres sure set point.

3. Crack open manual bypass valve to initially pres-

surize the system while simultaneously controlling
P

1

pressure through manual actuation of bypass

valve.

SECTION VI

5. Open the outlet (downstream) block valve.

6. Slowly open the inlet (upstream) block valve to

about 25% open, observing the inlet (up stream)
pres sure gauge. Determine if the reg u la tor is
fl owing. If not, slowly rotate the regulator ad just-
ing screw (1) CCW (viewed from above) until fl ow
be gins.

7. When

fl ow is established steady enough that the

inlet (upstream) block valve can be fully opened,
begin to slowly close the bypass valve if installed.

8. Develop

system

fl ow to a level near its expected

normal rate, and reset the regulator set point by
turning the adjusting screw (1) CW to increase
inlet pressure, or CCW to reduce inlet pres sure.

9. Reduce system fl ow to a minimum level and

observe pressure set point. Inlet pressure will
increase from the set point of Step 7. The maxi-
mum build in inlet pressure on increasing fl ow
should not exceed the stated upper limit of the
range spring by greater than 30%. If it does,
consult factory.

SECTION IV

SECTION V

down, closing the port; as inlet pres sure increases,
the diaphragm pushes up and the port opens.

2. A complete diaphragm failure will cause the reg u-

la tor to fail close and fl uid will discharge from the
spring chamber vent hole.

4. Closely monitor inlet (up stream) pressure via

gauge to ensure not over-pressurizing. NOTE: If
no bypass valve is in stalled, extra caution should
be used in start ing up a cold system; i.e. do ev-
erything slowly.

CAUTION

Do not walk away and leave a bypassed reg u -
la tor unattended!

VI. SHUTDOWN

1. On systems with a bypass valve, and where sys-

tem pressure is to be maintained as the reg u la tor
is shut down, slowly open the bypass valve while
closing the inlet (up stream) block valve. Fully
close the inlet (upstream) block valve. (When on
bypass, the system pressure must be con stant ly
observed and manually regulated.)

2. Remove range spring compression by turning

the adjusting screw (1) CCW to reduce the inlet
pressure.

3. Close the outlet (downstream) block valve.

4. Relieve the trapped upstream and down stream

pres sure.

5. The regulator may now be disassembled for

inspection and pre ven ta tive main te nance while
in-line.

CAUTION

Do not walk away and leave a bypassed reg u la-
tor unattended!