Cashco 521 User Manual

Page 14

Advertising
background image

IOM-521

14

SECTION VII

VII. TROUBLE-SHOOTING GUIDE:

1. Valve is "jumpy" in stroking.

Possible Causes

Remedies

A. Excess packing friction.

A1. Re-align body--stem--actuator.
A2. Packing follower too tight; back packing gland nut out.
A3. Install positioner.
A4. Increase bench set by changing to stiffer actuator range spring. May require

positioner if not installed. May require different airset.

B. Installed

backwards.

B. Install

per

fl ow arrow. Direction is only FTO.

2. Valve/actuator makes "screeching" noise.

Possible Causes

Remedies

A. Excess pressure drop.

A. Bring pressure drop within design limits.

3. Valve exhibits "excess" vibration.

Possible Causes

Remedies

A. Excess pressure drop.

A. Bring pressure drop within design limits.

B. Excessive cavitation in liquid service.

B. Change operation parameters to relieve causes of cavitation.

C. High outlet velocity.

C1. Reduce fl ow rate and/or pressure drop.
C2. Use multiple valves in series or parallel.
C3. Increase outlet pipe size.
C4. Use larger valve body with reduced trim.

4. Valve exhibits "excess" seat leakage.

Possible Causes

Remedies

A. Excess pressure drop.

A1. Reduce pressure drop conditions.
A2. Convert to reduced trim.
A3. Increase actuator thrust by changing actuator range spring.

B. Excess body and/or plug wear.

B1. Oversized valve operating too close to seat; go to reduced trim.
B2. Remove abrasive particulate.
B3. Possible excess cavitation in liquid service. Change operation parameters.
B4. Replace body assembly if seat is badly worn. Replace plug if badly worn.

5. Bonnet gasket leakage.

Possible Causes

Remedies

A. Improper bonnet bolting drawdown.

A1. Remove bonnet taking necessary safety precautions. Inspect bellows to

determine if primary seal at body/bellows is damaged. If bellows is damaged,

replace

bellows.

A2. Inspect secondary seal bonnet gasket for uneven thickness.

Replace bonnet gasket.

A3. Draw down bonnet bolting evenly and in a cross pattern; use bonnet bolting

torque levels indicated herein.

B. Cantilevered actuator.

B1. Do not allow use of the actuator as a "step" upon which personnel may climb.
B2. Do not "set" any added weight on the actuator.
B3. Install vertically.

6. Body fl ange leakage.

Possible Causes

Remedies

A. Over-tightening

fl ange bolting.

A. Loosen bolting, replace/install new gasket, retighten fl ange bolting in s
cross-pattern

evenly.

B. Improper pipe supports and anchors.

B. Provide piping anchors and guides at control valve station.

Restrain bending movements.

C. Corroded

fl ange bolting.

C. Replace with corrosion resistant fl ange bolting.

D. Used outside pressure/temperature limits.

D. Bring process variables within range of application; see Graph 1 in 521-TB.

Advertising