Terminal Assignments

Fig.: si794 C terminal assignments

Installation and connection

Installation instructions
Caution!

Danger of electric shock!

Any work on the electrical installation may only be undertaken by

experienced and qualified personnel in accordance with the applicable

local safety regulations.

• Always disconnect power to the device when making any electrical

connections!

• Be sure to follow the instructions in the user manual!

• Only connect the power supply when all internal wirings have been

completed and the system is correctly grounded!

When using an external voltage supply, always connect a ground-fault

circuit interrupter (tripping current max. 30 mA) between mains and

controller system! A ground-fault circuit interrupter is not required

when safety extra-low voltages (24 V DC supply via rechargeable

batteries or 24 V DC/AC supply through an isolation transformer)!

When operating the system outdoors, connect a surge voltage

protection between mains and controller system!

The terminals are suitable for single wires and flexible leads up to

2.5 mm² (AWG 14). Attach end ferrules to the leads.