7100 Series

Installation Instructions

7100 SERIES INDUCTIVE SLOT SENSOR

All 7100 Series flowmeters may be fitted with one inductive slot
sensor. Inductive slot sensors are 2-wire, DC, low current devices
and are designed to be used with a remote barrier / switch isolator
capable of powering the sensor and providing the desired switch-
ing option(s). Barrier / switch isolators are available with 220 VAC,
110 VAC or 24 VDC supply voltage requirements, contain single
pole double throw (SPDT) relays, and are DIN rail mountable. (Only
24 VDC units are actually powered by the rail.) See barrier / switch
isolator specifications for electrical connections and further details.

INDUCTIVE SLOT SENSOR-ELECTRICAL
SPECIFICATIONS

TYPE: Inductive
SUPPLY VOLTAGE:

5-25V DC (Switch Isolator)

OUTPUT: NAMUR
OUTPUT LOAD CURRENT:

<= 1mA-Float Present

>= 3mA (15mA Max.)-Float Absent

SWITCHING FREQUENCY:

5kHZ

HOUSING RATING:

IP67

WIRING:

2 Conductor, NAMUR

POS=BROWN / NEG=BLUE

TERMINALS: #1=POS / #2=NEG

PEPPERL+FUCHS: UL:

General Purpose

SENSOR APPROVALS: CSA: General Purpose

SETTING ALARM TRIGGER POINTS

1) Remove the two screws securing the ALARM ADJUST-SLOT
COVER & GASKET.
2) Remove the ALARM ADJUSTING-SLOT PLUG & GASKET.
3) Use a small screwdriver to adjust the ALARM SET POINTER to the
desired flow / alarm trigger point. MOVE UP AND DOWN ONLY.
CAUTION: DO NOT push in or pull on the ALARM SET POINTER.
4) Once you have the ALARM SET POINTER set to the desired trigger
point you may replace the ALARM ADJUST SLOT COVER & GASKET.
5) Replace the screws to secure the ALARM ADJUST-SLOT COVER &
GASKET.

Installation Instructions

7100 SERIES ASSEMBLY WITH OUTLET VALVE
PARTS LIST:

1. Meter Tube Assembly
2. Case Assembly
3. Meter Tube

Assembly Screw

4. Rear Case Screw Plug
5. Scale Plate
6. Follower Disc/

Pointer Assembly

7. Pointer Assembly

Screw
8. Case Cover Gasket
9. Case Cover
10. Case Cover Screw
11. Valve O-Ring
12. Valve Assembly

7100 SERIES ASSEMBLY WITH ALARM
PARTS LIST:

1. Case and Meter

Tube Assembly

2. Alarm Spacer
3. Alarm Set Pointer

and Sensor

4. Alarm Tension Spring
5. Alarm Retainer Clip
6. Follower Disc/

Pointer Assembly

7. Pointer Assembly
Screw

8. Case Cover Gasket
9. Case Cover
10. Case Cover Screw
11. Alarm Adjust Slot Gasket
12. Slot Cover
13. Alarm Adjust Slot

Cover Screw

14. Alarm Connector

12700 Pala Drive, Garden Grove, CA 92841

www.kinginstrumentco.com / (714) 891-0008

Meters are warranted against defects in materials and workmanship

to the original user for a period of thirteen (13) months from the date

of factory shipment, provided the meter is installed, operated and

maintained in accordance with King Instrument Company's

instructions and recommendations.

This warranty does not apply if failure is caused or contributed to by

any of the following: improper handling, improper storage, abuse,

unsuitable application of the product, lack of reasonable and

necessary maintenance, use exceeding suggested pressure and

temperature maximums, improper packaging for return, or repairs

made or attempted to be made by anyone other than King Instrument

Company, Inc.

KING INSTRUMENT COMPANY, INC. MAKES NO

WARRANTY AS TO THE FITNESS OF ITS PRODUCTS

FOR SPECIFIC APPLICATIONS.

This warranty is valid for the original end-user only and does not

apply to products that have been damaged or modified. This

warranty is non-transferrable and is limited to replacement or repair.

The liability of King Instrument Company arising out of its supply of

the products, or their use, shall not in any case exceed the cost of

correcting defects in the products as set forth above.

THIS WARRANTY IS A LIMITED WARRANTY AND

SHALL BE IN LIEU OF ANY OTHER WARRANTIES,

EXPRESSED OR IMPLIED, INCLUDING BUT NOT

LIMITED TO ANY IMPLIED WARRANTY OR

MERCHANTABILITY OR FITNESS FOR A PARTICULAR

PURPOSE. THERE ARE NO OTHER WARRANTIES

WHICH EXIST BEYOND THE DESCRIPTION OR FACE

HEREOF.

IN NO EVENT SHALL KING INSTRUMENT COMPANY BE

LIABLE FOR LOSS OF PROFITS, INDIRECT,

CONSEQUENTIAL OR INCIDENTAL DAMAGES.

Products should be returned, prepaid, to King Instrument Company,

Inc. with proof of purchase. Call factory for Return Merchandise

Authorization (RMA) number and return instructions.

2013A

METER TUBE ASSEMBLY

CASE ASSEMBLY

SCREW

REAR CASE SCREW PLUG

METER TUBE ASSEMBLY

SCALE PLATE

POINTER ASSEMBLY

POINTER ASSEMBLY

CASE COVER GASKET

CASE COVER

FOLLOWER DISC/

SCREW

2X

2X

2X

4X

CASE COVER

SCREW

VALVE O-RING

VALVE ASSEMBLY

All 7100 Series flowmeters may be fitted with one inductive slot sensor.

Inductive slot sensors are 2-wire, DC, low current devices and are designed to

be used with a remote barrier / switch isolator capable of powering the sensor

and providing the desired switching option(s). Barrier / switch isolators are

available with 220VAC, 110VAC or 24VDC supply voltage requirements, contain

single pole double throw (SPDT) relays, and are DIN rail mountable. (Only

24VDC units are actually powered by the rail.) See barrier / switch isolator

specifications for electrical connections and further details.

INDUCTIVE SLOT SENSOR-ELECTRICAL SPECIFICATIONS

TYPE:
SUPPLY VOLTAGE:
OUTPUT:
OUTPUT LOAD CURRENT:

Inductive

5-25V DC (Switch Isolator)

NAMUR
<= 1mA-Float Present

>= 3mA (15mA Max.)-Float Absent

SWITCHING FREQUENCY:

5kHZ

HOUSING RATING:

IP67

WIRING:

2 Conductor, NAMUR

POS=BROWN / NEG=BLUE

TERMINALS: #1=POS / #2=NEG

PEPPERL+FUCHS

General Purpose

General Purpose

UL:

CSA:

SENSOR APPROVALS:

SETTING ALARM TRIGGER POINTS:

1) Remove the two screws securing the ALARM ADJUST-SLOT COVER &

GASKET .

2) Remove the ALARM ADJUSTING-SLOT COVER & GASKET.
3) Use a small screwdriver to adjust the ALARM SET POINTER to the desired

flow / alarm trigger point. MOVE UP AND DOWN ONLY.

CAUTION: DO NOT push in or pull on the ALARM SET POINTER.

4) Once you have the ALARM SET POINTER set to the desired trigger point you

may replace the ALARM ADJUST SLOT COVER & GASKET.
5) Replace the screws to secure the ALARM ADJUST-SLOT COVER & GASKET.

ALARM SPACER

AND SENSOR

ALARM TENSION SPRING

ALARM SET POINTER

ALARM RETAINER CLIP

POINTER ASSEMBLY
POINTER ASSEMBLY

CASE COVER GASKET

CASE COVER

FOLLOWER DISC/

SCREW

4X

CASE COVER

SCREW

ALARM ADJUST SLOT GASKET

ALARM ADJUST SLOT COVER

ALARM CONNECTOR

ASSEMBLY

CASE AND METER TUBE

ALARM ADJUST SLOT COVER

SCREW

2X

12700 Pala Drive, Garden Grove, CA 92841

www.kinginstrumentco.com / (714) 891-0008

Meters are warranted against defects in materials and workmanship

to the original user for a period of thirteen (13) months from the date

of factory shipment, provided the meter is installed, operated and

maintained in accordance with King Instrument Company's

instructions and recommendations.

This warranty does not apply if failure is caused or contributed to by

any of the following: improper handling, improper storage, abuse,

unsuitable application of the product, lack of reasonable and

necessary maintenance, use exceeding suggested pressure and

temperature maximums, improper packaging for return, or repairs

made or attempted to be made by anyone other than King Instrument

Company, Inc.

KING INSTRUMENT COMPANY, INC. MAKES NO

WARRANTY AS TO THE FITNESS OF ITS PRODUCTS

FOR SPECIFIC APPLICATIONS.

This warranty is valid for the original end-user only and does not

apply to products that have been damaged or modified. This

warranty is non-transferrable and is limited to replacement or repair.

The liability of King Instrument Company arising out of its supply of

the products, or their use, shall not in any case exceed the cost of

correcting defects in the products as set forth above.

THIS WARRANTY IS A LIMITED WARRANTY AND

SHALL BE IN LIEU OF ANY OTHER WARRANTIES,

EXPRESSED OR IMPLIED, INCLUDING BUT NOT

LIMITED TO ANY IMPLIED WARRANTY OR

MERCHANTABILITY OR FITNESS FOR A PARTICULAR

PURPOSE. THERE ARE NO OTHER WARRANTIES

WHICH EXIST BEYOND THE DESCRIPTION OR FACE

HEREOF.

IN NO EVENT SHALL KING INSTRUMENT COMPANY BE

LIABLE FOR LOSS OF PROFITS, INDIRECT,

CONSEQUENTIAL OR INCIDENTAL DAMAGES.

Products should be returned, prepaid, to King Instrument Company,

Inc. with proof of purchase. Call factory for Return Merchandise

Authorization (RMA) number and return instructions.

2013A

METER TUBE ASSEMBLY

CASE ASSEMBLY

SCREW

REAR CASE SCREW PLUG

METER TUBE ASSEMBLY

SCALE PLATE

POINTER ASSEMBLY

POINTER ASSEMBLY

CASE COVER GASKET

CASE COVER

FOLLOWER DISC/

SCREW

2X

2X

2X

4X

CASE COVER

SCREW

VALVE O-RING

VALVE ASSEMBLY

All 7100 Series flowmeters may be fitted with one inductive slot sensor.

Inductive slot sensors are 2-wire, DC, low current devices and are designed to

be used with a remote barrier / switch isolator capable of powering the sensor

and providing the desired switching option(s). Barrier / switch isolators are

available with 220VAC, 110VAC or 24VDC supply voltage requirements, contain

single pole double throw (SPDT) relays, and are DIN rail mountable. (Only

24VDC units are actually powered by the rail.) See barrier / switch isolator

specifications for electrical connections and further details.

INDUCTIVE SLOT SENSOR-ELECTRICAL SPECIFICATIONS

TYPE:
SUPPLY VOLTAGE:
OUTPUT:
OUTPUT LOAD CURRENT:

Inductive

5-25V DC (Switch Isolator)

NAMUR
<= 1mA-Float Present

>= 3mA (15mA Max.)-Float Absent

SWITCHING FREQUENCY:

5kHZ

HOUSING RATING:

IP67

WIRING:

2 Conductor, NAMUR

POS=BROWN / NEG=BLUE

TERMINALS: #1=POS / #2=NEG

PEPPERL+FUCHS

General Purpose

General Purpose

UL:

CSA:

SENSOR APPROVALS:

SETTING ALARM TRIGGER POINTS:

1) Remove the two screws securing the ALARM ADJUST-SLOT COVER &

GASKET .

2) Remove the ALARM ADJUSTING-SLOT COVER & GASKET.
3) Use a small screwdriver to adjust the ALARM SET POINTER to the desired

flow / alarm trigger point. MOVE UP AND DOWN ONLY.

CAUTION: DO NOT push in or pull on the ALARM SET POINTER.

4) Once you have the ALARM SET POINTER set to the desired trigger point you

may replace the ALARM ADJUST SLOT COVER & GASKET.
5) Replace the screws to secure the ALARM ADJUST-SLOT COVER & GASKET.

ALARM SPACER

AND SENSOR

ALARM TENSION SPRING

ALARM SET POINTER

ALARM RETAINER CLIP

POINTER ASSEMBLY
POINTER ASSEMBLY

CASE COVER GASKET

CASE COVER

FOLLOWER DISC/

SCREW

4X

CASE COVER

SCREW

ALARM ADJUST SLOT GASKET

ALARM ADJUST SLOT COVER

ALARM CONNECTOR

ASSEMBLY

CASE AND METER TUBE

ALARM ADJUST SLOT COVER

SCREW

2X