CSB Battery HRL1210W User Manual

Hrl 1210w, 12v 10w, Powered by

Advertising
background image

14.4 to 15.0 VDC/unit Average at 25 (77 )

Cells per unit
Voltage per unit
Capacity

Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range

Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging

Current Limit
Equalization and Cycle Service
Self Discharge

Terminal

Container Material

6
12
10W @ 15min-rate to 1.67V per cell @25

o

C(77

o

F)

Approx.1.1 kg(2.43 lbs)
40A(5sec)
Approx. 35

m

25

o

C±3

o

C (77

o

F±5

o

F)

1A

CSB Batteries can be stored for more than 6 months at
25

o

C (77

o

F). Please charge batteries before using. For

higher temperatures the time interval will be shorter.
F2-Faston Tab 250
ABS(UL 94-HB) & Flammability resistance of

(UL 94-V0) can be available upon request.

Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )

Constant Power Discharge Characteristics Unit:W (25

,77 )

Constant Current Discharge Characteristics Unit:A (25

,77 )

HRL 1210W

12V 10W

Specification

Powered by

HRL 1210W is specially designed for high efficient discharge

application. Its characteristics are high energy density, small

footprint and high discharge efficiency. It can be used for more

than 260 cycles at 100% discharge in cycle service, up to 8

years in standby service.

13.5 to 13.8 VDC/unit Average at 25 (77 )

Width (W)

Dimensions :

Unit: mm (inch)

Overall Height (H)

Container height (h)

Length

(L)

70.0±1.0 (2.76±0.04)

64.0±1.0 (2.52±0.04)

178.0±2.0 (7.01±0.08) 34.0±1.0 (1.34±0.04)

F.V/Time

2MIN

4MIN

6MIN

8MIN

10MIN

15MIN

20MIN

30MIN

60MIN

90MIN

1.60V

19.2

13.7

10.5

8.84

7.47

5.51

4.24

3.06

1.66

1.29

1.67V

18.3

13.3

10.2

8.70

7.37

5.43

4.20

3.03

1.64

1.28

1.70V

17.9

13.0

10.1

8.64

7.32

5.39

4.18

3.02

1.63

1.27

1.75V

17.1

12.5

9.85

8.37

7.15

5.27

4.10

2.98

1.62

1.26

1.80V

16.3

11.8

9.50

8.10

6.98

5.14

4.02

2.93

1.60

1.25

1.85V

15.6

11.1

9.15

7.83

6.81

5.02

3.94

2.89

1.59

1.24

F.V/Time

2MIN

4MIN

6MIN

8MIN

10MIN

15MIN

20MIN

30MIN

60MIN

90MIN

1.60V

200

147

113

95.6

81.5

60.9

47.0

34.1

18.7

14.7

1.67V

193

143

110

94.0

80.5

60.0

46.5

34.0

18.6

14.6

1.70V

189

140

108

92.9

79.8

59.3

46.3

33.9

18.5

14.5

1.75V

182

134

106

91.0

78.9

58.5

46.0

33.5

18.4

14.4

1.80V

175

128

103

89.1

77.3

57.2

45.2

33.0

18.2

14.3

1.85V

169

121

100

86.6

75.8

55.8

44.5

32.6

18.1

14.2

CSB-manufactured

VRLA

batteries are UL-

recognized components

under UL1989.

CSB is also certified by
ISO 9001 and ISO 14001.

(http://www.csb-battery.com)

by TUV CERT according to ISO 9001,ISO 14001.

The system of manufacturer was certified

RA1308

Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.