CSB Battery HRL12110W User Manual

Powered by

Advertising
background image

I1-Thread lead alloy recessed terminal to accept M5 bolt

13.5 to 13.8 VDC/unit Average at 25 (77 )

14.4 to 15.0 VDC/unit Average at 25 (77 )

Cells per unit
Voltage per unit

Capacity

Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range

Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging

Current Limit
Equalization and Cycle Service
Self Discharge

Terminal

Container Material

6
12

110W @ 15min-rate to 1.67V per cell @25

o

C(77

o

F)

Approx.9.9 kg(21.83 lbs)
225A (5sec)
Approx. 9

m

25

o

C±3

o

C (77

o

F±5

o

F)

11A

CSB Batteries can be stored for more than 6 months at
25

o

C (77

o

F). Please charge batteries before using. For

higher temperatures the time interval will be shorter.

ABS(UL 94-HB) & Flammability resistance of

(UL 94-V0) can be available upon request.

Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )

Constant Power Discharge Characteristics Unit:W (25

,77 )

Constant Current Discharge Characteristics Unit:A (25

,77 )

HRL 12110W

12V 110W

Specification

Powered by

HRL 12110W is specially designed for high efficient discharge

application. Its characteristics are high energy density, small

footprint and high discharge efficiency. It can be used for more

than 260 cycles at 100% discharge in cycle service, up to 10

years in standby service.

Width (W)

Dimensions :

Unit: mm (inch)

Overall Height (H)

Container height (h)

Length (L)

175.0±2.0 (6.90±0.08)

--

166.0±2.0 (6.54±0.08)

125.0±1.5 (4.93±0.06)

F.V/Time

2MIN

4MIN

6MIN

8MIN

10MIN

15MIN

20MIN

30MIN

60MIN

90MIN

1.60V

170

145

118

97.5

81.6

61.4

48.0

33.6

21.3

14.9

1.67V

151

129

108

91.1

77.5

59.6

47.0

33.2

20.8

14.7

1.70V

141

121

103

88.3

75.7

58.6

46.3

32.7

20.4

14.5

1.75V

125

108

93.2

82.7

72.2

56.1

44.7

32.3

20.0

14.4

1.80V

109

94.0

83.7

76.4

68.7

53.7

42.5

31.9

19.6

14.2

1.85V

89.3

78.7

73.6

69.2

64.4

51.0

40.8

29.7

18.3

14.0

F.V/Time

2MIN

4MIN

6MIN

8MIN

10MIN

15MIN

20MIN

30MIN

60MIN

90MIN

1.60V

1,806

1,541

1,270

1,053

888

682

554

385

247

174

1.67V

1,624

1,386

1,171

988

852

665

535

377

243

173

1.70V

1,530

1,316

1,107

956

827

655

526

372

239

171

1.75V

1,358

1,190

1,020

900

796

636

510

361

234

170

1.80V

1,177

1,054

941

851

764

610

495

352

229

168

1.85V

995

918

854

793

733

589

478

337

217

167

CSB-manufactured

VRLA

batteries are UL-

recognized components

under UL1989.

CSB is also certified by
ISO 9001 and ISO 14001.

A

(http://www.csb-battery.com)

by TUV CERT according to ISO 9001,ISO 14001.

The system of manufacturer was certified

RA1308

Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.

Advertising
Table of contents