CSB Battery HRL12500W User Manual

Powered by

Advertising
background image

PPE(UL94-V0)*Flammability resistance can

be available upon request.

I2-Thread lead alloy recessed terminal to accept M6/M8 bolt

13.5 to 13.8 VDC/unit Average at 25 (77 )

14.4 to 15.0 VDC/unit Average at 25 (77 )

Cells per unit
Voltage per unit
Capacity

Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range

Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging

Current Limit
Equalization and Cycle Service
Self Discharge

Terminal

Container Material

6
12
500W @ 15min-rate to 1.67V per cell @25

o

C(77

o

F)

Approx.45.7 kg(100.75 lbs)
800A(5sec)
Approx. 3.7

m

25

o

C±3

o

C (77

o

F±5

o

F)

50A

CSB Batteries can be stored for more than 6 months at
25

o

C (77

o

F). Please charge batteries before using. For

higher temperatures the time interval will be shorter.

Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )

Constant Power Discharge Characteristics Unit:W (25

,77 )

Constant Current Discharge Characteristics Unit:A (25

,77 )

HRL 12500W

12V 500W

Specification

Powered by

HRL 12500W is specially designed for high efficient discharge

application. Its characteristics are high energy density, small

footprint and high discharge efficiency. It can be used for more

than 260 cycles at 100% discharge in cycle service, up to 10

years in standby service.

Width (W)

Dimensions :

Unit: mm (inch)

Overall Height (H)

Container height (h)

Length (L)

277.7±2.5(10.93±0.10)

274.7±2.5 (10.81±0.10) 343.0 ±2.5 (13.50±0.10) 170.0±2.0 (6.69±0.08)

F.V/Time

5MIN

7.5MIN

10MIN

15MIN

20MIN

30MIN

40MIN

50MIN

60MIN

90MIN

1.60V

491

444

388

294

235

172

136

112

95.7

67.2

1.67V

449

405

356

278

223

164

134

110

94.3

66.1

1.70V

425

386

340

270

217

161

133

109

93.5

65.4

1.75V

388

348

310

253

206

155

130

107

91.1

64.5

1.80V

348

309

278

233

194

147

123

102

87.3

62.0

1.85V

304

270

247

211

179

140

115

95.3

81.1

57.3

F.V/Time

5MIN

7.5MIN

10MIN

15MIN

20MIN

30MIN

40MIN

50MIN

60MIN

90MIN

1.60V

5,275

4,691

4,167

3,181

2,594

1,951

1,558

1,292

1,112

783

1.67V

4,880

4,300

3,790

3,018

2,490

1,871

1,520

1,276

1,091

769

1.70V

4,640

4,110

3,610

2,932

2,422

1,829

1,507

1,258

1,083

763

1.75V

4,250

3,750

3,290

2,748

2,309

1,740

1,466

1,237

1,066

754

1.80V

3,830

3,340

2,950

2,497

2,138

1,657

1,390

1,186

1,025

731

1.85V

3,366

2,882

2,600

2,203

1,964

1,564

1,321

1,130

977

695

CSB-manufactured

VRLA

batteries are UL-

recognized components

under UL1989.

CSB is also certified by
ISO 9001 and ISO 14001.

RA1308

Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.

Advertising
Table of contents