Polypropylene

(UL94-V0)*Flammability resistance can

be available upon request.

I2-Thread lead alloy recessed terminal to accept M6 bolt

13.5 to 13.8 VDC/unit Average at 25 (77 )

14.4 to 15.0 VDC/unit Average at 25 (77 )

Cells per unit
Voltage per unit
Capacity

Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range

Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging

Current Limit
Equalization and Cycle Service
Self Discharge

Terminal

Container Material

6
12
540W @ 15min-rate to 1.67V per cell @25

o

C(77

o

F)

Approx.43.9 kg(96.7 lbs)
800A(5sec)
Approx. 4

m

25

o

C±3

o

C (77

o

F±5

o

F)

54A

CSB Batteries can be stored for more than 6 months at
25

o

C (77

o

F). Please charge batteries before using. For

higher temperatures the time interval will be shorter.

Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )

Constant Power Discharge Characteristics Unit:W (25

,77 )

Constant Current Discharge Characteristics Unit:A (25

,77 )

HRL 12540W

12V 540W

Specification

Powered by

HRL 12540W is specially designed for high efficient discharge

application. Its characteristics are high energy density, small

footprint and high discharge efficiency. It can be used for more

than 260 cycles at 100% discharge in cycle service, up to 10

years in standby service.

Width (W)

Dimensions :

Unit: mm (inch)

Overall Height (H)

Container height (h)

Length (L)

275.7±2.5(10.85±0.1)

273.2±2.5 (10.76±0.1)

343±2.5 (13.5±0.1)

170±2 (6.69±0.08)

F.V/Time

2MIN

4MIN

6MIN

8MIN

10MIN

15MIN

20MIN

30MIN

60MIN

90MIN

1.60V

720

572

498

436

394

308

256

187

106

75.5

1.67V

608

517

452

406

370

294

245

181

105

74.3

1.70V

564

493

430

392

354

286

240

178

103

73.8

1.75V

501

440

398

365

327

270

228

172

101

72.0

1.80V

430

391

362

323

296

252

209

161

97.9

70.3

1.85V

379

340

304

282

265

222

187

147

90.3

66.2

F.V/Time 2MIN

4MIN

6MIN

8MIN

10MIN

15MIN

20MIN

30MIN

60MIN

90MIN

1.60V

6874

5883

5176

4688

4186

3421

2716

2057

1224

885

1.67V

6207

5325

4794

4282

3885

3250

2630

2006

1210

865

1.70V

5768

4937

4544

4016

3661

3097

2564

1988

1201

863

1.75V

5225

4639

4196

3766

3472

2951

2454

1925

1174

849

1.80V

4561

4310

3818

3442

3233

2723

2306

1846

1129

824

1.85V

4227

3643

3356

3146

3010

2443

2104

1715

1061

784

RA1311

Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.