GPIO Hardware Reference

Option Switches & Jumpers

CTI Products, Inc.

5. Option Switches & Jumpers

Addressing and option switches are provided for module configuration. The
module must be power cycled or reset after these switches are set so that the
options will take effect. Press the Reset toggle switch down to reset the module.

5.1 Group & Module Switches

The Group and Module rotary selector switches are used to set the node address
during module installation. Each module must have a unique Group:Module
address. Refer to the Monitor and Control Network System Manual, S2-60425, for
details about address planning or the Custom System Configuration
documentation for pre-assigned addresses if your system is a Custom Engineered
system.

SWITCH DESCRIPTION

DEFAULT

GROUP

Unit Address setting (00-FE)

refer to the MCN System Manual

00

MODULE

Unit Address setting (0-F)

refer to the MCN System Manual

0

Table 4 – Group & Module Switches

5.2 Option Switches

This section applies only if magnetically-latched relays are installed in the GPIO.

The Option switches allow the technician to pre-set any magnetically-latched
relay outputs that are installed in the GPIO module.

OPTION

SWITCH

DESCRIPTION Notes

Default

1 Not

used

Down

2 Not

used

Down

Reset Initial State

See

Table 6

Down

3

Reset Initialize Enable

See

Table 6

Down

4

Table 5 - Option Switches

Option Switches 3 & 4 are used to select the initial state at power-up and reset:

SW3

SW4

Initial State on Power Up or Reset

Default

Down

Down

Do not re-initialize. Use last stored state.

X

Up

Down

Do not re-initialize. Use last stored state.

Down

Up

Initialize to OFF

Up

Up

Initialize to ON

Table 6 – Initial State on Reset