DESCRIPTION

LED STATUS

In BOLD the normal state with gate closed and working

ON STEADY

OFF

BLINKING

1

LED BATTERY

Board working on AC

power

Board working on

battery power or ext

supply

Battery charging

2

LED +24

Main power present

Main power OFF

3

LED SET-UP

Normal operation

SLOW BLINK

(1 sec. ON - 1 sec. OFF)

SET-UP needed

FAST BLINK

(0.5 sec. ON - 0.5 sec OFF)

SET UP in in progress

4

LED ERROR

Board malfunction

No errors

Error conditions. See LED ERROR

DISPLAY table

5

LED BUS_MON

Communication on

Bus “2easy” OK

Communication bus

“2Easy” inactive. Verify

the bus “2Easy” devices

for shorts

Bus 2Easy devices with the

Same address. Verify dip switch

Setting on photocells or

Encoder LEDs

6

LED USB

Software update done

or USB key not present

USB key inserted and software

Update in progress

(DON’T Remove the USB key)

7

RESERVED

8

LED DL 14

OPEN A INPUT (N.O.)

OPEN A active

OPEN A not active

LED DL 15

OPEN B INPUT (N.O.)

OPEN B active

OPEN B not active

LED DL 16

STOP INPUT (N.C.)

STOP non active

STOP active or

wiring error

LED DL 17

FSW CL INPUT (N.C.)

Closing safety

devices clear

Closing safety devices

triggered or wiring error

LED DL 18

FSW OP INPUT (N.C.)

Opening safety

devices clear

Opening safety devices

triggered or wiring error

9

LED DL 19 FCA1

OPEN LIMIT SWITCH MO-

TOR1 (N.C.)

Limit switch

OFF or not used

Limit Switch activated

LED DL 20 FCC1

CLOSE LIMIT SWITCH MO-

TOR1 (N.C.)

Limit switch

OFF or not used

Limit Switch activated

10

LED DL 21 FCA2

OPEN LIMIT SWITCH MO-

TOR2 (N.C.)

Limit switch

OFF or not used

Limit Switch activated

LED DL 22 FCC2

CLOSE LIMIT SWITCH MO-

TOR2 (N.C.)

Limit switch

OFF or not used

Limit Switch activated

A11

E024U CONTROL BOARD