2.3.2 CONTACT

SENSORS

• Disconnect power to the gate operator before installing the contact sensors.
• Connect the contact sensors as shown below to the auxiliary terminal strip. Note that all

commons connect to main terminal 12.

• Contact sensors must be located at the leading edge, trailing edge, and post mounted both

inside and outside of the vehicular sliding gate. Additional contact sensors may be added for
additional protection where an entrapment zone may exist.

• Hardwired contact sensors must be located and wiring arranged so that the communication

between the sensor and the gate operator is not subjected to mechanical damage.

• Inputs from sensing edges/receiver to circuit board are NORMALLY OPEN.
• Diagram does not show power wiring to RF receiver.

Roadway

Fence

Gate

Open Photo-Beam

Close Photo- Beam

Open Edge

Close Edge

Alarm Reset

Alarm Signal

Auxiliary

Terminal Strip

Contact Sensor Wiring Diagram

Notes:

Inputs from sensing edges/receiver to circuit
board are Normally Open (N.O.).

Diagram does not show power wiring to RF
receiver.

If using contact sensors as the secondary
entrapment protection device, the UL Standard
specifies that one or more sensors be located at
the leading edge, trailing edge, and post mounted
both inside and outside of a vehicular horizontal
slide gate.

Trailing

Edge

Leading

Edge

Inside

Post Mount

Outside

Post Mount

Lead

Edge

TX

Trail

Edge

TX

Tra

il Ed

ge

Le

ad

Ed

g

e

2 CH

Rec'vr

In

si

d

e

P

o

s

t

Outs

ide

P

o

st

Trailing

edge
relay

Leading

edge
relay

Main Terminal 12

Common

Figure 27