5) Technical Specification

Power Supply Unit 5 Amp / 10 Amp
Input Supply

240v AC (+/- 10%) 50/60Hz

Input Fuse

1 - 10 Zone

5Amp, 25mm UK Type quick blow.

11 Zones +

13 Amp, 25mm UK Type quick blow.


Power Supply Unit Outputs
Voltage

Load: 24v DC (+/- 5%)

Battery Charger: 27.6v DC


Load

Zones 1 -5. 1 Amp single output as standard

Battery

Charge:

1

Amp

maximum


Fuses
Input to PCB

Fuse no. FS4.

5 Amp 20mm x 5mm quick blow.


Load Output

Fuse no. FS2.

3 Amp Single output as standard

20mm

x

5mm

quick

blow


Battery

Fuse no. FS1.

3 Amp 20m x 5mm quick blow.


Deep discharge protection is a feature on all models. This will cut off the battery supply to the load at 18v.

Standby Batteries
Capacity

Up

to

17Ah


Types

2 x 12v sealed lead acid batteries from Yuasa or other similar manufacturers.


Max. charge current

1 Amp


Max load output current

5 Amp


Quiescent standby drain

xxmA @ 24v DC


Note: two 12v Batteries are required. It is important that both batteries are the same size and of the same age and condition to
give the maximum performance.

Indicators
Enclosure Front Panel

Green LED lit shows Mains AC supply present.

Amber

LED

lit

shows

common

fault.


PCB

LED2

Green

lit

when

LED4

Green

lit

when

LED3

Yellow

lit

when

LED5

Yellow

lit

when

LED6

Yellow

lit

when


Fault Monitoring
Main fail

LED2 and lid-card green LED out

Battery not charging

LED4 green stays off

Battery short circuit

LED4 green stays off

Battery

missing

LED

3

lights

Battery fuse blown

LED 3 lights

Battery

low

LED

3

lights


Fault relay has a set of volt free contacts. It deactivates on any fault condition.

Operating ambient temperature range
-5°C to +45°C subject to battery operating range

Relative Humidity
95% Non-condensing (max)