Dscl, Industrial loop isolators and transmitters, Dscl specifications – Impulse DSCL20 User Manual

Page 2: Ordering information

Advertising
background image

DSCL

Visit our website www.dataforth.com

163

Industrial Loop Isolators and Transmitters

DSCL

Specifications

Module

DSCL20

Typical at T

A

=+25°C

Ordering Information

Model Input Range Output Range

DSCL20-01 0-20mA (4-20mA) 0-20mA (4-20mA)

DSCL20-02 0-20mA (4-20mA) 0-20mA (4-20mA)

DSCX-01

Socket for DSCL20-02

Model Description

Accessory

Figure 2: DSCL20-02 (Straight Pins)

Figure 1: DSCL20-01 (Bent Pins)

NOTES:

(1) Additional error <0.2% at 500

load

(2) V

in

=I

O

R

L

+ <2V

Figure 3: DSCX-01 Socket and Hold-down Accessory for DSCL20-02

(Straight Pin Modules)

Input Range

0/4-20mA

Input Current

50mA max at 18V max

CMV Input to Output

500Vrms, 1 Minute

Accuracy

(1)

(at 100

Load)

±0.05% Span Typical

±0.1% Span Max

Non-linearity

Included in Accuracy

Stability

<50ppm/°C

Overshoot

<20

µ

A (Typical 5

µ

A)

Compliance Voltage

18V ±5% max (with Zener Diode)

Voltage drop

(2)

<2V (for 500

Load)

Output Range

0/4-20mA

Limit Upper Range

30mA

Bandwidth, -3dB

750Hz

CMR (50Hz or 60Hz)

90dB

NMR

20dB per Decade Above 750Hz

Response Time

1ms, to 90% Span

Load Resistance Range

0-600

Output Noise

<20mV Peak-to-Peak (Typical <5mV)

Environmental

Weight Approximately 1.5g

Housing Material

Lexan 940 (UL 94 V-O)

Shock Test

50g (10 Shocks, 3 Axis)

Operating Temp Range

-20°C to +65°C

Storage Temp Range

-40°C to +85°C

Relative Humidity

0 to 75% Noncondensing

Emissions

EN50081-2 (Radiated, Conducted)

Immunity

EN50082-2 (ESD, RF, EFT)

Advertising