Card Setup

Address Selection

The DIO-104.REL contains several jumper straps for each port that must be set for
proper operation.

The DIO-104.REL occupies 4 consecutive I/O locations. The DIP-switch (S1) is
used to set the base address for these locations. Be careful when selecting the base
address as some selections conflict with existing PC ports. The following table
shows several examples that usually do not cause a conflict. To maintain
compatibility with other Sealevel Systems I/O adapters, the actual port addresses are
found at BaseAddress+2 (Relays K1-K8) and BaseAddress+3 (Relays K9-K16).

Address Binary

Switch

Settings

A9 A8 A7 A6 A5 A4

A3 A2

1 2 3 4 5 6 7 8

100-103 01

0000

00xx

On Off

On On On On

On On

104-107 01

0000

01xx

On Off

On On On On

On Off

200-204 10

0000

00xx

Off

On On On On On

On On

280-283 10

1000

00xx

Off

On Off

On On On

On On

284-287 10

1000

01xx

Off

On Off

On On On

On Off

2EC-2EF 10

1110

11xx

Off

On Off

Off

Off

On

Off Off

300-303 11

0000

00xx

Off

Off

On On On On

On On

320-323 11

0010

00xx

Off

Off

On On Off

On

On On

388-38B 11

1000

10xx

Off

Off

Off

On On On

Off On

3A0-3A3 11

1010

00xx

Off

Off

Off

On Off

On

On On

3A4-3A7 11

1010

01xx

Off

Off

Off

On Off

On

On Off



The following illustration shows the correlation between the DIP-switch setting and
the address bits used to determine the base address. In the example below, address
300 is selected as the base address. Address 300 in binary is XX 11 0000 00XX
where X = a non-selectable address bit.

1 2 3 4 5 6 7

ON

OFF

A9

A2

8

Note: Setting the switch ‘On’ or ‘Closed’ corresponds to a ‘0’ in the address, while
leaving it ‘Off’ or ‘Open’ corresponds to a ‘1’.