Laurel Electronics Modbus Protocol For Series 2 Laureate Digital Panel Meters, Counters, Timers & DIN-Rail Transmitters User Manual

Page 6

Advertising
background image

- 6 -

USB Board &
Basic Ethernet Board

No jumpers needed.

RS232 Board

e - Normal operation.
f - Slave display to RS232 from another meter.

g - Pull-up resistor on RTS line.

Note: Board is shipped with jumpers e and g installed

RS485-Modbus Board, Full Duplex Operation

b & e - Bias jumpers should be installed on 1 board.
a & d - Installed on last meter in long cable run.

RS485-Modbus Board, Half Duplex Operation

b & e - bias jumpers installed on 1 board.
c & f - installed for half duplex operation.
a - installed on last meter in line with long cable runs.

Note: Board is shipped with no jumpers installed.

Modbus

b

a

c

d

e

RJ45

RJ45

f

RS485 Board, Full Duplex Operation

b & d - Installed on last meter in long cable run.

RS485 Board, Half Duplex Operation

a & c - Installed for half duplex operation.
d - Installed on last meter in line with long cable runs.

Note: Board is shipped with no jumpers installed.

Ethernet-to-RS485 Converter Board
& USB-to-RS485 Converter Board

Full Duplex Operation

No jumpers for short cable runs.
Add b & d for long cable runs.

Half Duplex Operation

a & c for short cable runs.
d - Installed on last meter in line with long cable runs.

3. CONNECTOR WIRING, SERIAL BOARD TO COMPUTER