Laurel Electronics Custom ASCII Protocol For Laureate Series 2 Digital Panel Meters, Counters, Timers & L-Series Transmitters User Manual

Page 35

Advertising
background image

35

0B (U)

Alarm Confg2

Bit 7 6 5 4 3 2 1 0 Alarm Trigger Delay

60 Hz

50Hz

0 0 0

0.018s

0.021s

0 0 1

0.035

0.043

0 1 0

0.07

0.085

0 1 1

0.14

0.17

1 0 0

0.28

0.34

1 0 1

0.56

0.68

1 1 0

1.13

1.36

1 1 1

2.27

2.72

0 0 0

Al1 Band Dev, Al2 Band Dev

0 0 1

Al1 Hysteresis, Al2 Band Dev

0 1 0

Al1 Band Dev, Al2 Hysteresis

0 1 1

Al1 Hysteresis, Al2 Hysteresis

1 0 0

No deviation in menus or calc

0A (U)

Alarm Confg1

Bit 7 6 5 4 3 2 1 0

0 0 0 0 Al1 Hi active, Al2 Hi active

0 0 0 1 Al1 Lo active, Al2 Hi active

0 0 1 0 Al1 Disabled, Al2 Hi active

0 1 0 0 Al1 Hi active, Al2 Lo active

0 1 0 1 Al1 Lo active, Al2 Lo active

0 1 1 0 Al1 disabled, Al2 Lo active

1 0 0 0 Al1 Hi active, Al2 disabled

1 0 0 1 Al1 Lo active, Al2 disabled

1 0 1 0 Al1 disabled, Al2 disabled

0 0

Al1 & Al2 non-latching

0 1

Al1 latching, Al2 non-latching

1 0

Al1 non-latching, Al2 latching

1 1

Al1 & Al2 latching

0 0 Relay1 On when Al1 active, Relay2 On when Al2 active

0 1 Relay1 Off when Al1 active, Relay2 On when Al2 active

1 0 Relay1 On when Al1 active, Relay2 Off when Al2 active

1 1 Relay1 Off when Al1 active, Relay2 Off when Al2 active