Optical air & vapor eliminators, Optical air and vapor eliminator installations – Liquid Controls LCR-II Installation E3655-E3656 User Manual

Page 23

Advertising
background image

23

oPTICal aIr & vaPor elIMInaTors

Optical Air Eliminator:

Refined Fuels

Optical Vapor Eliminator:

LPG and NH

3

S3

S3 Solenoid

Optical Sensor

LectroCount LCR-II

Gallons

Meter System with Optical Vapor Eliminator

Meter System with Optical Air Eliminator

optical air and vapor eliminator

Installations

When ordered as part of a meter system with a LCR-

II, Liquid Control’s optical air and vapor eliminators

are bolted onto the strainer and wired to the LCR-II

at the factory. Optical air and vapor eliminators can

also be ordered separately and installed onto meter

systems already in service. For mechanical installation

instructions, refer to the manual specific to the optical

air and vapor eliminator. Instructions for wiring optical air

and vapor eliminators to the LCR-II are provided on this

page.

Materials needed for wiring valves:

not supplied

with the air or vapor eliminator

20 AWG stranded wire (2 for the S3 solenoid valve)

Weatherproof flexible conduit, ½" diameter and ½" NPT

conduit connectors or cable glands

PTFE tape or pipe sealant

To wire optical air and vapor eliminators to the

lCr-II:

1. Attach cable glands and/or conduit connectors to the S3

solenoid valve, the optical sensor, and the LCR ports.

2. Thread the 20 AWG wires through a piece of

weatherproof conduit cut-to-length from the S3 solenoid

to a LCR-II port.

3. Run the weatherproof conduit between the S3 solenoid-

operated valve and the LCR-II housing. Pull the wires

through the ports, and tighten the connectors. Liquid

Controls recommends running the optical sensor wire

through weatherproof conduit as well.

4. Connect the three 20 AWG wires to the S3 solenoid-

operated valve terminals and to terminals 52 and 53 on

the j15 terminal block of the LCR-II CPU board.

5. Connect the optical sensor wires to terminals 54, 55, and

56 on the j15 terminal block of the LCR-II CPU board.

Disconnect the power before working on the CPU board.

Disconnect Power

Advertising