Page: 23

DOC#: MN-IT400-R2d.doc

18.4 Edit High Temperature Limit

The maximum valid temperature before triggering a high temperature warning.
Note:
After setting a high limit, a display of I NVALI D indicates the low was not less
than the high.

18.5 Temperature delay

The number of seconds to wait between temperature measurements. The shorter
the delay, the more accurately the temperature profile will represent the flow.
Shorter delay periods reduce battery life (when powered exclusively by battery). To edit the delay,
turn the

Number

dial to select from one of the pre-programmed values, or select 75 (dial position 9)

and edit the number for a custom delay. In Run Mode, the temperature annunciator will flash each
time the temperature is sampled.

19. Test

The test menu allows the viewing, testing, and simulating of various system inputs
and outputs. Here is a listing of the test items:

1. r aw f r eQ – The displayed value is the raw input frequency (autoranged) being received by the

flowmeter input. The value is in Hz. Pressing

Select

displays the max frequency received by

the flowmeter input.

2. r t d ohm – The displayed value is the raw resistance value of the RTD in ohms. The value is

indeterminate if no RTD is installed.

3. bat t er y / - DC I N- / - Loop- – The displayed value is the battery voltage (if BATTERY is

displayed) or internal voltage regulator if - DC I n- or - Loop- is displayed.

4. LCD t est – Pressing

Select

causes the IT400’s LCD to indicate all segments.

5. 4- 20t est – Pressing

Select

causes the IT400 to simulate five values on the 4-20mA output.

The

Number

dial is used to step through the following values: 0%, 25%, 50%, 75%, & 100%.

The backlight will be disabled during the 4-20mA output test so as to not affect the 4-20mA
output. The dial must be turned until one of the values is displayed.

6. ver sI on – The displayed value is the internal software version.

20. Menu Lockout Enable

Enables or disables the menu lockout. If the menu lockout is disabled, the menu is
exited and RUN mode is resumed.

20.1 Menu Lockout Code

Displays and allows the edit of the code that must be entered to gain access to the
menu. A code of 0000 disables the lockout. Edit the number to read the desired
lockout code setting. Only four digits are available for the lockout code. The default lockout code is
1000.

t est

ENABLED

LoC

1000

CoDE

10

DELAY

200

.

00000