Lightronics AT402 User Manual

At series architectural dimmer

Advertising
background image

Page

1

of

8

AT SERIES ARCHITECTURAL DIMMER

Revision 0.1

OWNERS MANUAL

08/29/2003

www.lightronics.com

Lightronics Inc.

509 Central Drive Virginia Beach, VA 23454

tel 757 486 3588



DESCRIPTION OF UNIT

The AT Series Dimmer is a unit specifically optimized for architecural applications. It can be supplied with up to
four 2400 Watt lighting circuits (channels) and be remotely controlled by a DMX lighting console. Some models
are provided with a fast acting 20 Amp magnetic circuit breaker for each channel. A table at the end of this
manual gives a description of the different model numbers. Additional models can be supplied for 220 VAC
operation.

The unit is intended for wall mounting. AT Series dimmers are for INDOOR USE ONLY.

POWER REQUIREMENTS

The AT Series dimmer requires a 120VAC hot power feed line for each lighting circuit (channel), a common
neutral, and an earth ground. Each of these feeds must powered by a circuit providing a minimum of 20 Amps
and supplies only one of the AT Series dimmer lighting circuits. The power feed for channel 1 also powers the
unit's internal electronic circuitry. The internal circuitry is protected by a replacable 1/2 Amp, 250 Volt, fast acting
fuse. The AT dimmer may be operated from either single phase or three phase power and may be switched
between these power types by the user.

INSTALLATION

































1
2
3
4

1
2
3
4

120VAC

POWER IN

LIGHTING

LOADS

1/2AMP FUSE

AND SPARE

1

2

3

4

CIRCUIT

BREAKERS

NEUTRALS

GROUNDS

PROGRAMMING

CONTROLS

AND DISPLAY

CIRCUIT

BOARD

AT-402 FRONT VIEW (Cover Removed)

CONTROL

TERMINAL STRIP