Mastercool 69110 AUTOMOTIVE A-C RECOVERY SYSTEM User Manual

Page 3

Advertising
background image

3

be obtained from refrigerant manufacturers.
Attention: Technicians using this equipment must be certified under EPA Section 609 (Environmental Protection Agency).
WARNING: There is the possibility of refrigerant and equipment contamination from hydrocarbons or leak
sealants in the refrigerant container or the mobile A/C system being serviced or refrigerant container. Before
recycling use proper equipment such as a refrigerant identifier, to insure R134a refrigerant only. Refrigerants
other than R134a require special handling by someone with specific expertise and equipment.
NOTE: Use only new refrigerant oil to replace the amount removed during the recycling process. Used oil should
be discarded per applicable federal, state, and local requirements.
The manufacturer shall not be responsible for any additional costs associated with a product failure including,
but not limited to, loss of work time, loss of refrigerant, cross contamination of refrigerant, and unauthorized
shipping and/or labor charges.
IMPORTANT: R134a systems have special fittings (per SAE specifications) to avoid cross-contamination with R12
systems. DO NOT adapt your unit for a different refrigerant — system failure will result.
PERIODICALLY INSPECT AND MAINTAIN REFRIGERANT HOSES AND SEALS TO ENSURE THAT HOSES AND SEALS
PREVENT THE ADDITION OF EXCESS AIR, DUE TO LEAKS, DURING THE RECOVERY PROCESS, WHICH WOULD
INCREASE THE NCG LEVEL IN THE RECOVERED REFRIGERANT.
All hoses used for interconnecting system should have shut off valves (manual or automatic) on both ends. Treat all hoses
and connections with caution. Hoses or connections will contain liquid refrigerant or gas under pressure. Connect and
disconnect fittings with caution.
The Recovery System includes a fine screen filter at the inlet port. Screen should be checked often or
whenever contamination prevents proper operation of recovery system.

OPERATING GUIDE FOR DIRECT VAPOR OR LIQUID RECOVERY (Refer to fig.1)

Note: A. If recovery machine shuts off due to full tank, close valve on tank and shut off machine. Replace and connect
empty recovery tank to yellow hose and restart Recovery Machine. If Recovery Machine does not start refer to
Steps 10 and 11.
B. The recovery procedure should operate for 28 minutes. If the procedure stops before 28 minutes of operation,
wait 5 minutes and check for low side pressure rise. If the pressure rises, repeat the recovery procedure until
the pressure stays below atmospheric.
1. Make sure on-off switch is off, “O” pushed in. Connect system to grounded power connection.
2. Turn INLET (blue color) valve to CLOSE position. Turn center valve (yellow color) to RECOVER position.
3. Connect blue and red hose to inlet “T” fitting on recovery machine. Hoses have shut-off valves on both ends.
4. Connect blue hose from low side system connection to inlet port. Connect red hose from high side system connection
to inlet port. A “T” fitting is provided at inlet port to connect both the blue and red hose.
5. Connect yellow hose from outlet port of recovery machine to vapor (gas) connection on recovery tank.
6. Connect float switch cable from recovery machine to recovery tank.

NOTE: Recovery system will not operate if float switch cable is not connected. Recovery tank must be

Mastercool part #67011 and have a maximum capacity switch to prevent over filling of tank. Purge air and
moisture from system by bleeding lines or use a vacuum pump.
7. Open the vapor valve on the recovery tank.
8. Turn OUTLET (red color) valve to OPEN position.
9. Turn INLET valve on Recovery System to OPEN.
10. Turn the Recovery System on (push power switch “I”). If the Recovery system fails to start, turn the power switch
off. Turn inlet valve to PURGE. Turn center valve to PURGE. Rotate center valve between PURGE and RECOVER to get
the inlet and outlet pressures within 70 PSI of each other. Leave the center valve in the RECOVER position. Turn the
power switch on. If the Recovery System starts, immediately turn the inlet valve to OPEN. If the Recovery System still
does not start, repeat the above procedure.
11. Observe operation of system. In rare instances “slugging” may be apparent (loud compressor noise or high vibration).
If this condition is apparent turn inlet valve to LIQUID position. System can be run with this setting continuously. It is
suggested that operator periodically turn inlet valve to OPEN position and check for proper operation of system. Best
operation of the system is with inlet valve OPEN and automatic pressure regulating valve controlling flow conditions.
12. When the inlet pressure is 15” Hg or more, the recovery is done. To purge the Recovery System, leave the system
running. Turn the center valve to PURGE. Turn the inlet valve to PURGE. It may take 1 or 2 minutes to purge the
Recovery machine of refrigerant, depending on how much liquid is in it.
13. If draining the oil, turn the machine off between 10 PSI and 2 PSI. Otherwise, let the Recovery system run until it
reaches 15” Hg or more, or the low pressure switch turns the Recovery system off.
14. Make sure the Recovery system is off. Turn the inlet and outlet valves to CLOSE. Close the valve on the tank and