Mastercool 99663*A HVAC Digital Manifold User Manual

Page 2

Advertising
background image

BATTERY INSTALLATION
Remove the battery compartment cover. Make
sure to place the battery into the compartment
with the correct polarity. Replace battery cover.

PRESSURE ADJUSTMENT FOR ELEVATION

For an accurate reading, it is important to
adjust the manifold for elevation and
barometric pressure. Follow these steps to set
the unit for local elevation and barometric readings.
1. Press the

POWER button to turn the unit ON.

2. Allow 10-15 seconds for unit to initialize. (You will see all characters and units
countdown 99999,88888,77777... ) Once initialization is complete, only
pressure and temperature readings will appear.

NOTE: Certain refrigerants do not have a temperature display at a given pressure.

In order to achieve an accurate pressure and temperature reading it is recommended to
press and hold the ENTER button for 8 - 10 seconds and then release. Pressure readings
will now be truly zero. Due to environmental factors such as elevation, temperature and
humidity, you should complete this process each time you turn the unit on to read pressure
or vacuum. DO NOT ATTEMPT TO ZERO UNIT OUT WHILE UNDER PRESSURE.

WARNING! If the manifold is connected to a pressure or vacuum source

and displays actual readings, do not attempt to zero out the reading by

pressing the enter button. This can offset the reading.

SETTING REFRIGERANT, PRESSURE, TEMPERATURE AND AUTO-OFF

• Press the

POWER button to turn the unit ON. Wait for the unit to initialize [a refrigerant,

pressure, temperature or vacuum will be displayed when the unit is ready].
• Press the

SELECT button to access the REFRIGERANT MENU.

Press

SELECT again to display refrigerant type.

[To scroll through the refrigerants press the

select/

or vacuum/↓ button: R11, R12,

R13, R21, R22, R23, R32, R113, R114, R115, R116, R123A, R124, R125, R134, R134a,
R141B, R142B, R143, R143A, R152A, R176, R218, R290, R401A, R401B, R401C, R402A,
R402B, R403A, R403B, R404A, R405A, R406A, R407A, R407B, R407C, R407D, R408A,
R409A, R410A, R410B, R411A, R411B, R412A, R413A, R414A, R414B, R415A, R417A
(ISCEON MO59), R422A (ISCEON MO79), R422D (ISCEON MO29), R427A (FX100), R500,
R501, R502, R503, R504, R507A, R508B, R509A, R600, R600A, R601, R601A]
Press

ENTER to confirm the desired refrigerant.

• Next the PRESSURE UNIT will display.
Press the

SELECT button to change the pressure unit. Press ENTER to confirm.

• Next the TEMPERATURE UNIT will display.
Press the

SELECT button to either °F or °C. Press ENTER to confirm.

• Next AUTO-OFF will display.
Press the

SELECT button to disable Auto-Off [auto-off will clear from the display.]

If the auto-off feature is displayed the manifold will shut down after 15 minutes. Press
the

ON/OFF button to turn the unit back on and allow 15-20 seconds to initialize.

NOTE: It is recommended to keep the auto-off feature enabled to save the life of

the battery.

SETTING VACUUM

• Connect the vacuum sensor cable to the manifold and turn the unit on.
• Press the

VACUUM button. This will phase out the temperature display and only show the

vacuum units.
Press the

SELECT button until the desired vacuum unit is displayed.

Press

ENTER to confirm.

• The vacuum display will automatically go off after 15 minutes. Press the

ON/OFF button

and

VACUUM button to turn the unit on. Allow 30-45 seconds for the sensor to warm up

and the correct vacuum reading to appear. (

If pressure, temperature or deep vacuum

is being used for an extended period of
time turn the unit off and turn back on
again when

reading is required.)

NOTE: To disconnect the vacuum sensor cable
be sure to press the release latch under the
connector cable. Pulling on the cable without
disengaging the latch will cause damage and
is not replaceable under warranty.
(SEE FIG. A)

IMPORTANT NOTES FOR SERVICING AC/R SYSTEM

A system that has been opened or one that is found to be excessively low on refrigerant
pressure as a result of a leak, must be fully evacuated by means of recovery/recycling and
deep vacuum. A system that has been evacuated must be repaired, leak tested and
evacuated again before charging.

DIAGNOSING THE SYSTEM PRESSURE AND TEMPERATURE

1. Make sure both valves on the manifold are closed (turn knobs clockwise).
2. Connect the blue and red hose from the low and high side of the manifold to the system.
3. Start the system and allow some time for the true pressure reading on the manifold to

3

FIG. A

�������������������

BATTERY COMPARTMENT

www.mastercool.com

Advertising