Rack/universal mount models, 6kva – MaxPower Corp UniStar P Rack User Manual

Page 5

Advertising
background image

Rack/Universal Mount Models

SC60021RM

SC60022RM

INPUT

Connection

Hardwire / Optional 6ft. Line Cord with L6 30P Plug

Voltage Range

160 -280Vac

Frequency

45 ~ 65 Hz

Phase/Wire

Single, Line + Common + Ground

Power Factor

Up to 0.99 at 100% Linear Load

Current THD

<5% at 100% Linear Load

OUTPUT

Connection

Hardwire

Hardwire

Voltage

208/120Vac or 240/120Vac

208/220/230/240Vac, Selectable 240/120, 208/120Vac

Voltage Adjustment

+/- 0%; +/- 1%; +/- 2%; +/- 3% For All Voltages

Voltage Regulation

+/- 2%

Capacity

6000VA/4200W

Parallel Capability

Redundancy or Capacity – 4 Units Maximum

Rated Power Factor

0.7 Lagging

Wave Form

Sine Wave, THD < 3% (no load to full load)

Frequency Stability

+/- 0.2% (Free Running)

Frequency Regulation

+/- 1 Hz

Transfer Time

0ms/instantaneous

Crest Factor

3:1

Effi ciency (AC to AC Nominal)

91%

Effi ciency (AC to AC ECO Mode)

Up to 97%

Leakage Current

< 3mA @ Full Load

DC Start

Yes

Cooling

Load Dependant Variable Speed Fans

DISPLAY, ALARMS, DIAGNOSTICS, COMMUNICATIONS & EMERGENCY FUNCTION

Status On LED + LCD

Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low,
Battery Bad/Disconnected, Overload, Transferring with interruption & UPS Fault

Readings On LED + LCD

Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage,
Battery Voltage & Unit’s Inner Temperature

Self-Diagnostics

Upon Power-on, Front Panel Setting & Software Control, 24 Hour self check

Audible Alarms and Visual

Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions

Communications

RS232 Serial Port ( 2 slots available for optional SNMP/WEB, USB or Dry Contact Card)

Emergency Power Off (EPO)
Connection

Emergency Power Off shuts down UPS when activated by customer supplied EPO Circuit

PHYSICAL

Dimensions (H x W x D) inches

3.5 x 17.3 x 26 (2U)

Weight (lbs.)

53

Safety and Performance

UL1778, c-UL; CE – FCC Class A, EN 50091-2, EN 62040-2, EN61000-3,

IEC 61000 (various), IEC 62040, CISPR 22

EXTERNAL BATTERY PACK – Module 2, Plug Connected to UPS Module (Note 1)

*Model

SC-BP6000RM-1 (same battery used for extended run times)

Battery Run Time @ Full Load

8 minutes

Type

Sealed Lead Acid Maintenance Free, 20 each 12V/7AH, 240Vdc

Hot – Swap Batteries

Yes

Recharge Time

4 hours to 90%

Battery Connection

Plug Connector

Extended Run Time Battery Packs

Yes

Dimensions (H x W x D)

5.25" x 17.3" x 26" (3U)

Weight (lbs.)

119

OUTPUT TRANSFORMER / MANUAL BYPASS SWITCH - Module 3, (Hardwired to UPS Module (Note 1)

Output Voltage

208/120Vac or 240/120Vac

208/120Vac or 240/120Vac

Manual Bypass Switch

Make – Before - Break

Dimensions (H x W x D)

3.5" x 17.3" x 26.0" (2U)

Weight (lbs.)

93

OPTIONAL POWER DISTRIBUTION UNIT (PDU) for Model SC60021RM ONLY! – Module 4 Optional (Hardwired to Transformer Module)

Model

SC-6RMPDU1

SC-6RMPDU2

Input Voltage of UPS Module

208 or 240Vac

208 or 240Vac

Output Voltage through

Receptacles

208/120Vac or 240/120Vac

208Vac or 240Vac

Output Receptacles

(1) L6-30R, (1) L5-30R, (1) L5-20R, & (2) 5-15/2020R

(1) L6-30R, (1) L6-20R & (4) 6-20R

Dimensions (H x W x D)

3.5" x 12.8" x 2.8" (2U)

Weight (lbs.)

7

OPTIONAL COMMUNICATION Cards with Shutdown Software

SC-SNMP1

SNMP/WEB Network Card and Shutdown Software

SC-Contact/EPO

Dry Contact & EPO Card

SC-PK

Parallel Cable kit contains two RJ45 cables and miscellaneous hardware for paralleling

Note: (2) slots available; both cards can be used simultaneously; RS232 Port is disabled when communication cards are installed.

OPTIONAL EXTENDED BATTERY PACK CHARGER

SC-CHG-1000

1000W External Mount Battery Charger (1) charger
per every (2) External Battery Packs Required

6.6"W x 11.1"D x 3.4"H

7 lbs.

OPTIONAL PARALLEL DISTRIBUTION / BYPASS MODULE

(Note 2)

SC-PKIT-2

Parallel Distribution Bypass 60Amp for (2) UPS Modules

10.5"W x 9.5"D x 3.7"H

11 lbs.

SC-PKIT-4

Parallel Distribution Bypass 120Amp for (4) UPS Modules

10.5"W x 16.4"D x 3.7"H

20 lbs.

Notes:
Modules 1, 2 & 3 make up a complete hardwired 208/120Vac or 240/120Vac output system.
Parallel for capacity confi gurations can use (1) battery system sized for the ultimate capacity.
Parallel for redundancy confi gurations require (1) battery system for each UPS.

6kVA

Rack/Universal Mount Models