Variety of customer options slots, Communications capability, Hot-swappable battery – MaxPower Corp UniStar P Tower User Manual

Page 4: Optional external battery charger, Matching extended battery pack, User personalization, Advanced battery management, Galvanic isolation transformer, Cold start function, The unistar

Advertising
background image

www.stacoenergy.com

Variety of Customer
Options Slots

This UPS also provides two customer

option communication slots in addition

to the standard RS232 port. All

com-munications cards are designed

for simple installation; electrical

connections are made through a

26-pin edge card connector. The

fi rst RS232 port on the rear panel will

remain active, even though optional

communication cards are installed.

Communications Capability

The UniStar

®

P is shipped with standard

monitoring/shutdown software. The

software allows control of the UPS and

graceful shutdown when the utility

power fails, but also allows the user to:

Remotely test the major operating

functions of the UPS

Communicate via SNMP/WEB card

Access UPS functions via the WEB

Hot-Swappable Battery

The UniStar

®

P allows users to replace

batteries without electric shock hazard,

while the UPS supplies continuous

power to your application.

Optional External
Battery Charger

The optional charger can be

installed for fast recharge of

the extended battery pack.

Power Output: 1000W

Mounting: UPS or wall mount

Matching Extended
Battery Pack

Optional matching battery packs

are available to easily extend the

UPS runtime to several hours.

User Personalization

Through the LCD front panel, you may

easily change the parameters and

settings built in to the DSP controllers,

such as UPS operation modes, voltage

confi gurations, synchronization

frequency windows (for use with

generators), bypass voltage tolerances

and audible alarm.

Advanced Battery Management

The UniStar

®

P automatically manages

the end of discharge voltage according

to load. This function prevents deep-

discharge of the built-in battery during

a power failure and saves battery life.

Galvanic Isolation Transformer

The galvanic isolation transformer

provides not only complete isolation

between the input and the output, but

also various secondary voltages, such

as 220/230/240 Vac, 208/120 Vac and

240/120 Vac.

Cold Start Function

Users can turn on the UPS without

utility power available.

6, 8 & 10kVA Single Phase UPS Tower
Extended Battery Run Times
(minutes)

Note: External 1000W Battery Charger (P/N SC-CHG-1000) required
every (2) External Battery Cabinets

40 X Cabinet (2 strings)

UPS

Size

Part

Number

Qty. of

Cabinets

25%

Load

50%

Load

75%

Load

100%

Load

6kVA

Internal

0

56

22

12

8

SC-BP6000T-2

1

226

95

56

38

2

420

180

109

75

3

629

273

166

116

4

847

370

226

158

5

1073

471

289

203

8kVA

Internal

0

64

21

12

7

SC-BP1100T-2

1

216

91

54

37

2

402

172

104

72

3

602

261

158

110

4

812

354

216

151

5

1028

451

276

194

10kVA

Internal

0

40

15

8

5

SC-BP1100T-2

1

164

68

40

27

2

307

131

78

54

3

461

198

120

83

4

623

270

154

114

5

790

345

210

147

60 X Cabinet (3 strings)

UPS

Size

Part

Number

Qty. of

Cabinets

25%

Load

50%

Load

75%

Load

100%

Load

6kVA

Internal

0

56

22

12

8

SC-BP6000T-3

1

321

137

82

56

2

629

273

106

116

3

959

420

257

180

4

1305

576

354

249

5

1660

737

454

321

8kVA

Internal

0

64

21

12

7

SC-BP1100T-3

1

307

131

78

54

2

602

261

158

110

3

919

402

246

172

4

1251

551

338

238

5

1594

706

435

307

10kVA

Internal

0

40

15

8

5

SC-BP1100T-3

1

234

98

58

40

2

461

198

120

83

3

706

307

187

130

4

963

422

258

181

5

1229

541

332

234