Model selection guide, Xprt-6kva xprt-10kva – MaxPower Corp XPRT Series User Manual

Page 2

Advertising
background image

XPC

USA / Denver, CO / [email protected]

XPC

EMEA / Rotterdam, NL / [email protected]

www.xpcc.com

©2014 Xtreme Power Conversion Corporation. All Rights Reserved. XPRT6.01U (Rev 3/6/13)

Protect your business.

XPRT-6kVA XPRT-10kVA

Backup time 1/2 load Full load 1/2 load Full load
UPS

14 5 16 6

+ (1) BP

34

14

39

17

+ (2) BP

58

25

66

28

+ (3) BP

82

36

92

41

+ (4) BP

105

47

119

54

XPRT-6kVA

XPRT-10kVA

PDU1 = Hardwired

PDU3 = (4)5-20R + (2)L5-20R + (2)L6-30R

PDU2* = (4)5-20R + (1)L6-30R + (1)L14-30R PDU10 = (8)5-20R + (2)L6-30R
PDU4* = (2)5-20R + (2)L6-20R

PDU11 = (4)5-20R + (4)L6-20R

PDU5* = (4)5-20R + (2)L6-30R

PDU12 = (4)5-20R + (4)L6-30R

PDU6* = (4)EN60320

PDU13 = (4)5-20R + (2)L6-20R + (2)L6-30R

PDU7* = (4)L5-20R + (2)L5-30R

PDU14 = (4)L5-20R + (4)L6-20R

PDU8* = (4)L5-20R + (2)L6-30R
PDU9* = (4)L6-20R

Optional PDU provides

output receptacles

OPTIONAL INTEGRATED BYPASS/PDUs

BATTERY RUNTIMES

Optional SNMP card

Maintenance

bypass switch

Integrated bypass/

PDU modules

Input and output terminal

blocks for hardwired

connections

For more information, visit

www.xpcc.com/xprt6-10

MODEL SELECTION GUIDE

MODEL NUMBER

XPRT-6kVA XPRT-10kVA

INPUT


OUTPUT






BATTERY

PHYSICAL

ENVIRONMENT

Capacity VA (W)

6000VA (4200W)

10000VA (8000W)

Voltage 208/120V, 240/120V auto-sensing; 230/115V, 200/100V selectable*
Frequency

40

70Hz

Power factor

> 0.97

Input connection

10ft cord with L14–30P plug or hardwire

Hardwire

Voltage 208/120V, 240/120V, 230/115V, 200/100V (selectable) ± 5%
Frequency

50/60Hz auto-sensing ± 5% or frequency converter

Output connections Integrated bypass/PDU with hardwired or receptacle options (options below)
Harmonic distortion

< 3% with linear load; < 5% with non-linear load

Wave form

Sine wave, zero transfer time

Efficiency AC/DC/AC

> 92%

Auto restart/start on battery

Yes

Overload capacity

110% for 300 sec; 130% for 30 sec; 200% for 5 sec

Crest factor

3:1 at full load

Battery type

(12) 9AH/144VDC

(24) 9AH/288VDC

Recharge time

< 3 hours to 90%

UPS dimensions (W x D x H)

16.9 x 22.5 x 6.9 in (4U)

16.9 x 26.0 x 10.6 in (6U)

Weight with internal battery

162 lbs

309 lbs

Battery pack (BP) dimensions

16.9 x 22.5 x 3.5 in (2U)

16.9 x 26.0 x 6.8 in (4U)

Battery pack weight

95 lbs

200 lbs

Operating temperature

32–104°F (0–40°C)

Audible noise

< 55dba

Altitude

11,500 ft above sea level

APPROVALS
WARRANTY
COMMUNICATIONS INTERFACE
AVAILABLE OPTIONS

UL, cUL, FCC

3 years electronics and battery (2 years outside of USA)

RS-232, EPO, and USB standard, SNMP (optional card)

PDUs, parallel tie/bypass panels options available

(Runtimes are shown in minutes and will vary based on battery age

and site conditions.)

Maintenance

bypass breaker

Removable 10kVA

power module

XPRT-6kVA rear view

XPRT-10kVA rear view

*Includes L14-30P input cord

*Capacity derates in certain configurations. See user manual for more details

Advertising