Available through – MaxPower Corp Toshiba 4200 FA CT User Manual

Page 2

Advertising
background image

UPS ADJUSTABLE SPEED DRIVES MOTORS CONTROLS INSTRUMENTATION PLC

INDUSTRIAL DIVISION

13131 West Little York Road, Houston, Texas 77041

Tel 713/466-0277 Fax 713/466-8773

US 800/231-1412 Canada 800/872-2192 Mexico 001/800/527-1204

www.toshiba.com/ind

Copyright 11/2006

Available Through:

UPS Cabinet

AC Output

208/120 V, 3 Ph/4 W,

50/60 Hz

Static Bypass Switch

AC Input

208 V, 3 Ph/4 W,

50/60 Hz

24x12 VDC=288 VDC

Maintenance Bypass Switch

Converter

DC Chopper/

Charger

SYNC

Inverter

Make-Before-Break

High

Freq.

Filter

High

Freq.

Filter

Contactor

MCCB

Contactor

������������������

*UPS4200FACT060331*

4200FA CT 15/25/30/50 kVA UPS

Model Number

T42F3F150XAMBN

T42F3F250XAMBN

T42F3F300XAMBN

T42F3F500XAMBN

Capacity

kVA/kW

15/12

25/20

30/24

50/40

Topology

True On-line, Double Conversion, IGBT Pwm, with Active Input Power Factor Correction

Input

Voltage

208/120 V, 3 Phase, 4 w + Gnd

Voltage Range

+10% to -30%; +20% to -30% online (without utilizing battery)

Power Factor

Greater than 0.99

Current THD

Less than 3%

Frequency

50/60 Hz (Range 45 to 65 Hz)

Current Limit

115% Maximum

Output

Voltage

208/120 V, 3-Phase, 4 w + Gnd

Frequency

50/60 Hz ± 0.01% (Can be Used as a Frequency Converter)

Voltage Regulation

< 1% Balanced, 100% Load Step / < 2% Unbalanced, 100% Load Step

Overload (Inverter)

125% for 90 Seconds, 150% for 30 Seconds

Overload (Bypass)

125% for 10 Minutes, 1000% for 10 Minutes per Second

Battery

Time (Full / Half Load)

10/30 Minutes

5/15 Minutes

3/10 Minutes

5/15 Minutes

DC Link

288 VDC

Ripple Voltage

< 0.5% DC

Environment

Temperature Range

0 to 40° C (Operating) / -20 to +50° C (Storage)

Relative Humidity

0 to 95% Non-Condensing

Heat Rejection

5733 BTUs

7100 BTUs

9100 BTUs

17737 BTUs

Efficiency

AC/DC/AC 87.7%, DC/AC 90%

AC/DC/AC 88.5%

Dimensions

Dimensions (L x D x H)

20” x 36.3” x 59.8”

35.4” x 37.6” x 59.8”

Weight (lb)

900

910

915

2548

Altitude

6600 ft (2000 m)

(Maximum without Derating)

Audible Noise

< 60 dBA at 1 m

< 65 dBA at 1 m

Features

Internal Make-Before-Break Maintenance Bypass Switch, RS232 and Dry Contact Interface

Standards

UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), NEMA PE1-1993

Warranty

(See Toshiba Warranty Policy for Full Details.)

Service

7 x 24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)