Product Features

Built-in closed loop cooling
can support high temperature
water and IT loads from 20 to
80 kW

Fully redundant cooling
system configuration with
self-adjusting valves, requires
only a mechanical hookup

Accepts low and high
temperature cooling water

Hot swappable and field
upgradable Heat eXchanger
(HX) units can support
multiple configurations

Hot swappable and alarmed
fan assemblies assure
continuous operations

Indoor/ Outdoor NEMA 4
enclosure provides superior
strength and protects
equipment from the elements

Shock and vibration isolation

Industry standard 19” wide x
42” deep racks are fully
adjustable

Built-in environmental
monitoring with optional IP
control and GUI interface

Options

EMI Shielding

Stand alone programmable
encrypted security system
with audit trail

16R insulation/fire protection

Fire protection using Novec
1230

Smart power distribution units
with outlet switching and
power monitoring

R.A.S.E.R. HD

The R.A.S.E.R. HD is available with blue or black powder coating.


Technical Specifications:
Dimensions.......................................................89

” tall x 47” wide x 64” long

Weight

………………………………………………………….....2000-2300 lbs*

Dynamic Load Capacity

……………………………………….……….2000 lbs

Operational Temperature……………………………………...…-40 to 130˚ F*
High Density Equipment Capacity

…………...………….….……...……...42U

Total Equipment Capacity

…………………………………………20 to 80 kW*

Heat Exchangers Available

………………………………...……Single 20 kW

…………………………………...…Single 40 kW

…………………………… …...……..Dual 20 kW

………………………………….…….Dual 40 kW

Water Connections Per Heat Exchanger

………………….…..Inlet 1½” NPT

…….……………...Outlet 1½” NPT

…...………....Condensate ½” NPT

Heat Exchanger Water Flow Per U

nit……………………..20 kW-12.5 GPM

…………….……...….40 kW-19 GPM

Internal Air Flow Per Heat Exchang

e……………………..20 kW-1750 CFM

...............................40 kW-2350 CFM
Water supply te

mperature………………………………………….43 to 90˚ F

All Capacity Ratings Based on

43˚ F Water Supply

* depending upon upgrade options selected

A/C Power Options:
Standard

– 208-230 VAC 50/60 Hz 20 kW-700 WATTS 40 kW-1200 WATTS

Optional

– 48 VDC 20 kW-624 WATTS 40 kW-1152 WATTS

230 Yuma St, Denver, CO 80223