Applications, Technical specifi cations – MaxPower Corp FirstLine 924 8, 12, 16kW User Manual

Page 2

Advertising
background image

Applications

Public Buildings

Theaters

Schools

Parking Garages

Housing Complexes

In the event of an AC power failure, FirstLine

®

924

automatically supports the connected lighting loads on
battery power and will continue to provide power without
any interruption for a full 90 minutes. When the utility power
returns to normal, FirstLine

®

924 will automatically recharge

the batteries to be ready for the next power disturbance.

Technical Specifi cations

Three-Phase Central Inverter for
Emergency Lighting Applications

General

On-line double-conversion topology

True sine wave output

Continuous, no-break operation

Three-phase system will support single

or three-phase loads

LCD front panel monitoring and control

Automatic system bypass

Input

Input Voltage Rating: 208Y/120 and

480Y/277 standard, Delta optional
with

transformer

Input Voltage Range: +/-10% system

start-up;

+10% /-15% operation

(166-250Vac,

384-576Vac)

Input frequency: 60Hz +/-5%

Full load walk-in from 25% to 100% of

rated load in <5 seconds

Surge Withstand: Meets IEEE C62.41

Output

IGBT: true sine wave PWM inverter

Inverter output distortion: <5% THD

(100%

non-linear)

Inverter output distortion: <2% THD

(linear

loads)

Voltage regulation: +/-1% of nominal

at full load

Frequency: 60 Hz

Battery

Designed for easy maintenance

Standard backup time of 90 minutes at

full

load

Valve-Regulated Lead-Acid (VRLA) battery

10 year design life at 77°F (25°C)

Quick recharging times

Housing

Freestanding, NEMA 1 steel enclosure

Front and top service access

Bottom access for conduit entries

Various battery cabinet confi gurations

Environmental

Agency Compliance: UL924, FCC and

CSPR22, Class A

Operating temperature range 18°F (-8°C)

to 104°F (40°C)

Acoustical Noise: 65 db at 3 feet

Relative Humidity: 0-95% non-condensing

Meets NFPA 101 Life Safety, and

NEC

codes

Seismic Zone 4 certifi ed

Monitoring/Communications

Front Panel LCD Display

4 x 16 character display

System status and alarms

Communications Port

RS-232

Dry Contact (AS/400)

Remote monitoring

SNMP available option

In addition to meeting

life safety requirements,

the FirstLine

®

924 can

also increase the life

expectancy of the

protected lighting system

and reduce long-term

cost of ownership.

Your tailored power solutions provider