MaxPower Corp GE LP11 UL 924 User Manual

Page 2

Advertising
background image

Modifications reserved

Page 2/5

TDS_LPE_11U_6K0_10K_1UL_V010.doc

Technical Data Sheet LP 11 924 Series 6 & 10 kVA

General data

Topology

VFI, double conversion

Nominal output rating

kVA/kW

6/4.8

10/8

Output power factor

Lag/Lead

0.8

0.8

Efficiency in double

conversion operating

mode (

linear resistive load

and fully charged battery

)

25% load

%

85.5

87.2

50% load

87.7

89.5

75% load

88.3

89.5

100% load

88.7

88.7

Heat dissipation in

double conversion

operating mode (

linear

resistive load and fully charged
battery

)

25% load

W (BTU/hr)

204 (695)

292 (997)

50% load

337 (1150)

468 (1596)

75% load

477 (1628)

705 (2404)

100% load

608 (2076)

1018 (3474)

Efficiency while

operating in eco mode

(

linear resistive load and fully

charged battery

) (

eco mode

not available in RPA

)

25% load

%

90.6

93.3

50% load

92.5

95

75% load

93.3

95.1

100% load

93

94.2

Heat dissipation while

operating in eco mode

(

linear resistive load and fully

charged battery

) (

eco mode

not available in RPA

)

25% load

W (BTU/hr)

120 (409)

120 (409)

50% load

190 (648)

190 (648)

75% load

220 (750)

270 (921)

100% load

360 (1228)

500 (1706)

Cooling air (25°C - 30°C)

m

3

/h (CFM)

330 (194) max.

Audible noise level (at 5 ft./1.5Mts)

dB(A)

40 at no load and 50 at 100% load

Operating temperature range

0°C - 40°C (32°F - 104°F); For optimal back up time 20°C - 30°C (68°F - 86°F) is

recommended for battery.

Storage temperature range

-20°C - 45°C (-4°F - 113°F)

Relative humidity

Max. 95% (non-condensing)

Protection degree

IP 20 (IEC 60529 and DIN 40050)

Safety

UL 924; IEC 60950, IEC 62040-1

EMC

FCC part 15 class A; IEC/EN 62040-2 Class A

Surge capacity

IEC 61000-4-5 (6kV 1.2/50 µsec –3kA 8/20µsec) & IEEE C62.41 (6kV, 100kHz)

Electrostatic discharge immunity

4kV contact / 8kV air discharge

Transport

On pallet / rollers for installation

Color

Cubicle: RAL 9010 (white) Front panel: RAL 9006 (aluminum)

Cable connections

On terminals, bottom-rear

Cooling

Forced by regulated internal fans

Input converter (rectifier + power factor correction)

Nominal AC input voltage

120V, 208V, 240V split phase, 277V. For 208 & 240V input, bottom transformer

cabinet is not required.

Input frequency range

40 - 70Hz

Power factor

> 0.99

THDi

<10%

Full load input current
(Charging current included)

Uin = 120V A

57

89

Uin = 208V A

33

51

Uin = 240V A

30

44

Uin = 277V A

23

39

Inrush current

None

DC output voltage

380 V