48 Configuration Parameters

The Communication Counters provide the following data:

Total Transactions

The total number of transactions performed on the E-
Port’s Modbus since the E-Port was powered up.

Total Errors

The total number of errors on the E-Port’s Modbus
since the E-Port was powered up. Errors indicate a
problem in the network wiring or the instrument’s
Modbus hardware.

It is normal for errors to be detected:

when a master E-Port to Backup E-Port
switchover occurs, or

when an instrument is disconnected, or

when an instrument address is changed

Modbus Status

Indicates whether the E-Port is in Active or Standby
mode. An E-Port will be in Standby mode if it is part of
a Master Backup E-Port configuration, and the other
associated E-Port is in Active mode.