Continuous Control Functions

RAMP SOAK BLOCK

3-10

Block Type
RSK

This is the Ramp/Soak type. Block type code is 56.

00

Version (VERSION) ........................................................................................................... – – R
The RSK block is at version 1.

01

Block Length (BLKLEN) .................................................................................................... – – R
Number of data base bytes used by this block. Could be as low as 68 with one segment or as
high as 533 with 36 segments and states and discrete inputs being used.

02

State (STATE) .................................................................................................................... CWR
All block state changes are reported as events. See IB-23G600 (I/O Logic Book 1) Section
2.4.1, State Changes
for additional information. Controls algorithm execution.

RUN

0

Normal Operation. Block is executed.

HOLD

1

Block is not executed. Qualities retain previous values.

OFF

2

Block is not executed. Qualities will be BAD.

DEBUG

3

Block is not executed. No fields are updated. Most attributes are
writeable.

03

Bad Inputs (BADINP)......................................................................................................... CWR
See Section 2.3.2, Data Quality for additional information.

REJECTED

0

The Process (PROCINP), Track Command (TCMDINP), Reset
(RESINP), Stop (STOPINP), Run (RUNINP), Hold (HOLDINP) and
Skip (SKIPINP) inputs are examined on every execution of the block.
If any of these inputs are bad, then the ramp soak block does not
update its outputs and the output qualities are set bad.

ACCEPTED

1

Block runs its algorithm without a check on input quality and output
quality is set to good.