4 remote i/o interface bus connections – Micromod MOD: Remote I/O Modules for use with 2020N Remote I/O Interface Module User Manual

Page 15

Advertising
background image



Remote I/O Modules

ELECTRICAL CONNECTIONS

3.4

REMOTE I/O INTERFACE BUS CONNECTIONS

The remote I/O Interface (CS 31) bus is a shield twisted pair RS485 connected as described
below. One 2020N Remote I/O Interface module is required for each remote I/O network.

REMOTE I/O INTERFACE RS485 SERIAL NETWORK

Bus Master

2020N Remote I/O Interface Module (end of bus)

Bus Slaves

Remote I/O Digital Modules

Maximum Length

500 meters (1600 feet)

Baud

Rate

187.5K

Number of Addresses 32 (31 slaves + 1 RIO master at address 0). Star connection

of the bus is forbidden!

Termination

120

Ω, 1/4 Watt resistor required across the two conductors

at each end of the cable (2 shipped with RIO module)

Shield

Required over 50 meters (160 feet). The shield of the bus
must be connected to the earth near the master. The shield
is connected to the earth through a capacitor 1 nF class Y.

Isolation

The bus is opto-isolated from all units.

REMOTE I/O INTERFACE CABLE
Indoor

Beldon

#9182

Indoor

Plenum

Beldon

#89182

Underground

Beldon #9815 twisted twinax

Outdoors above ground NOT recommended

Wiring

See

connection

guidelines


When noisy elements are in the area of the cabinet, it is better to connect the bus' shield to
the ground via a capacitor 1 nF class Y directly at the access of the cabinet according the
following diagram.


11