Micromod MOD: 30ML Quick Reference Guide User Manual

Reference card mod 30ml™ controller, Controller front panel

Advertising
background image

Reference Card

MOD 30ML™ Controller

MicroMod Automation, Inc.

75 Town Centre Dr.

Rochester, NY 14623 USA

Tel: (585) 321-9200

Fax: (585) 321-9291

928 Jaymor Road, Suite B-120

Southampton, PA 18966 USA

Tel: (215) 355-4377

Fax: (215) 355-4378

MicroMod Automation S. de R.L.

Mexico

Tel: (55) 57373402

Fax: (55) 57373402

WWW.MICROMODAUTOMATION.COM

Controller Front Panel

Alarm Light

Alarm Scroll
Key
Loop Tag

Display Scroll
or Escape
Line 2
Manual Key

Auto Key

Remote/
Local Key
Scroll Key

Up Key

/ = immediate
entry.
No slash =
Entry [ENT]
required.

Down Key

Process
Variable

Bar Graph

(Line 2)

Set-Point

Variable

Bar Graph

(Line 6)

Output

Bar Graph

(Line 6)

Line 1: Loop Tag Display
Line 2: Process Value and engineering units label.
Line 3: MAN = Manual

AUT = Auto
UAK = Unacknowledged Alarm
ACT = Active Acknowledged Alarm
UBQ = Unacknowledged Bad Quality
ABQ = Active Bad Quality
CLR = Acknowledged Alarm Clear
LHD = Local Hold (service switch set)

Line 4: LOC = Local

REM = Remote
TRK = Track
RET = Return (from alarm display)
PRV = Previous Step (Tune and Setup)

Line 5: OP = Output value on Line 6

SP = Set-Point value on Line 6
RA = Ratio value on Line 6
BI = Bias value on Line 6
FF = Feed Forward value on Line 6
RSP = Remote Set-Point value on Line 6
TUN = Alarm or Control Tune request
ENT = Enter Value (flashes while active)
NXT = Next Step (Tune and Setup)

Line 6: Line 5 value or Tune and Setup choices.

Service / Run Switch

RUN is the normal
operating position.

SERV. position puts
instrument in local hold
state (LHD) and only
*DEVICE* displays are
active.

RS-232 Port (if configured)
requires Application Builder.

READ/WRITE

READ ONLY

NORMAL

MODULE

LOAD

From Main Database to Memory
Module

1. Set switches to Read/Write and

Module Load.

2. Power up instrument.
3. UPLOAD? is displayed . Press

Up or Down key and Enter (scroll
key).

4. UPL DONE SET WP? is

displayed. Upload done. Set Write
Protect? by pressing Up key and
entering. Otherwise, skip this step.

5. Power down instrument and set

switches to Normal and
Read/Write or Read Only.

6. Power up instrument.

From Memory Module to Main Database

1. Set switches to Read/Write or Read Only and Normal.
2. Power up instrument.

The instrument automatically attempts a download

Line 1 / Line 2 Display

Line 6 Display / Entry

Entry point.

NONE, OUT CH 1, OUT CH 2, S01 to S11.
Only outputs not used elsewhere are listed.

0% of output range.

100% of output range.

Float 0 = X, Float 1 = X.X, Float 2 = X.XX,
and so forth to Float 6 = X.XXXXXX

Value determines lower output limit.

Value determines upper output limit.

Previous, Preset.

Any initial output value.

Exit point.

Entry point. Alarms.

Entry point. Process Value Alarms.

NONE, HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).

Value where input will cause the alarm to
become active.

Absolute offset to clear alarm.

0 = Suppress Unacknowledge, 1 to 255
defines priority level (1 is highest).

NONE, S01 to S11. Only unused shown.

Repeat Process Value Alarms setup for
2, 3 and 4.

Exit point. Process alarms.

Entry point. Deviation Alarms.
NONE, HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).

Value where input will cause the alarm to
become active.

Absolute offset to clear alarm.

0 = Suppress Unacknowledge, 1 to 255
defines priority level (1 is highest).

NONE, S01 to S11. Only unused shown.

Repeat setup for Deviation Alarm 2.

Exit point. Deviation Alarms.

Entry point. Output Alarms.

NONE, HIGHHIGH (>=), HIGH (>=),
LO (<=), LOW LOW (<=).

Value where input will cause the alarm to
become active.

Absolute offset to clear alarm.

0 = Suppress Unacknowledge, 1 to 255
defines priority level (1 is highest).

NONE, S01 to S11. Only unused shown.

Repeat setup for Output Alarm 2.

Exit point. Output Alarms.

Exit point. Alarms.

Exit point. Compound List (return to General
Template setup for next compound).

CTAG01 OUTPT

Output

OUTPUT SLOT

Output Slot Position

OUTPUT LO SIGNL

Output Low Signal

COMPOUND

OUTPUT HI SIGNL

Output High Signal

OUTPUT DISP FMT

Output Display Format

OUTPUT LO LIMIT

Output Low Limit

OUTPUT HI LIMIT

Output High Limit

RESTART TYPE

Output Restart Type

OUTPUT INIT VAL

Output Initial Value

CTAG01 ALARMS

Alarms

PV ALARMS

PV ALM 1 TYPE

Process Val. 1 Alarm Type

PV ALM 1 TRIP VAL

Trip Value

PV ALM 1 HYSTRSIS

Hysteresis

PV ALM 1 PRIORITY

Priority

ALARMS

DEVIATN ALARMS

DEVALM 1 TYPE

Deviation 1 Alarm Type

DEVALM 1 TRIP VAL

Trip Value

DEVALM 1 HYSTRSIS

Hysteresis

DEVALM 1 PRIORITY

Priority

PV ALM 1 DIG OUT

Digital Output

ALARMS

DEVALM 1 DIG OUT

Digital Output

OUTPUT ALARMS

OUTALM 1 TYPE

Output 1 Alarm Type

OUTALM 1 TRIP VAL

Trip Value

OUTALM 1 HYSTRSIS

Hysteresis

OUTALM 1 PRIORITY

Priority

ALARMS

OUTALM 1 DIG OUT

Digital Output

COMPOUND

COMPOUND LIST

The Company's policy is one of continuous
improvement and the right is reserved to modify
specifications without notice.
© 2004, MicroMod Automation Printed in USA

QRG-1800R

Issue 2

Line Display Description

Memory Module

UPLOAD:

DOWNLOAD: