Micromod MOD: Modcell 2050R 2051FZ2, Foxboro 62H to 2050R Conversion Accessory User Manual

Micromod Equipment

Advertising
background image

92902-92

2051F Conversion Instructions for Foxboro 62H

Conversion Instructions for

Foxboro 62H Conversion Accessory to MODCELL 2051R

Accessory Part Number: 2051FZ20000A



INTRODUCTION

This MODCELL 2051F conversion accessory allows a MODCELL 2051R Controller to fit into the Foxboro
62H instrument shelf.

Parts Included in Conversion Accessory

base bracket (1)

spring latches (2)

1/8 inch Pop-rivet (6)

Instructions (1)


Tools Required

Pop-rivet gun

Instrument screwdriver (small blade)


BRACKET MOUNTING PROCEDURE

The following steps describe how to install the Foxboro conversion brackets on to the instrument.
Removal of the MODCELL 2051R instrument from the instrument housing is not necessary.
1. Remove the contents of the conversion kit from its package and examine that all parts are present.

2. Locate the large black bracket to the bottom of the MODCELL 2051R, aligning the four 1/8 inch

holes. Orient the bracket as shown in Figure 1. Insert a pop rivet into each of the four holes and
secure the bracket in place using the pop-rivet gun.


3. Stack the two top latch brackets one on top of the other so the 1/8 inch holes align. Align the brackets

to the top front two 1/8 inch holes of the MODCELL 2051R instrument. Orient the bracket as shown in
Figure 1. Secure this bracket in place with the two remaining 1/8 inch pop-rivets.


PRE-CONFIGURATION FOR 10-50 mAMP...

If the old 10-50 milliamp transmitter and valve are to be left in service, the controller must be set up
accordingly. Ten to fifty milliamp installations require a separate (non 2-wire) transmitter power supply.

The MODCELL 2051R will not supply more than 22 milliamps to a transmitter. A transmitter power
supply may already be in place depending on you installation. A MODCELL 2051R's analog control
output will supply up to 54 milliamps to a 400 ohm load.

1. Remove the termination cover from the back of the MODCELL 2051R. Attach an instrument power

cable.


2. Replace the termination assembly cover and tighten in place. Apply power to the instrument.

3. Enter the "Base Config **Menu**" (see IB-23C650-_._), select "current" as the input type for the

process input.

1

Advertising