MODBUS RTU

COMUNICATIONS GUIDE

5

SOFTWARE BASICS

MASTER/SLAVE RELATIONSHIP

A MODBUS RTU system consists of a Master and one or more Slave devices. Multiple Masters are not
permitted on the same network. The Master is responsible for initiating all communications, therefore, no
peer-to-peer capability is supported. With some hardware, it is possible to dynamically switch the device
between Master and Slave modes. This capability allows multiple Masters, though not simultaneously. With
special hardware, such as Phoenix Digital’s MPE Plus, having multiple Masters is possible, though it limits the
communications to the basic “Standard” MODBUS commands. Using the MPE Plus will block extended
MODBUS communications, including the Application Builder.

MESSAGE RESPONSE TIMES

The MODBUS RTU protocol relies on precise timing for reliable communications. The message structure is
such that a 3.5 character or greater pause will be interpreted as the end of a message. The actual time
varies with the baud rate. Conversely, most devices require a defined minimum amount of time between
messages. Another factor to consider is that each device has its own response time. This response time can
be anywhere from a few milliseconds to a few hundred milliseconds. The Host must be configured to allow
adequate time for the slowest device to respond.

INSTRUMENT RESPONSE TIMES TO HOST COMMANDS

These times represent the maximum time from when the instrument receives a request from the master, to
when it begins to send the response.

Table 2. Instrument Response Times

Device

Max Response Time

Device

Max Response Time

C100

250 mSec

C1900

250 mSec

C150

250 mSec

Modcell MLP

60 mSec *

C200

250 mSec

2050R

100 mSec

C300

180 mSec

MOD30ML

60 mSec *

C310

160 mSec

MR250

125 mSec

C500

125 mSec

PR100

90 mSec

* NOTE:

The response times for Modcell MLP and MOD30ML are for read
messages. Write messages may take longer. These instruments have a
configurable Write Message Timeout parameter.