Required cable sizes, Installation – APC GALAXY 5000 User Manual

Page 15

Advertising
background image

34001813EN/AE

- Page 15

2. Installation

Required cable sizes

Cable sizes are determined for copper conductors (for aluminium conductors, increase the size by 30%). Size

calculations also take into account a voltage of 400 V and grouping of four cables.

UPS power

rating

Minimum sizes for

separate Normal AC
input copper cables

(<100 m)

Minimum sizes for

separate Bypass
AC input copper

cables (<100 m)

Minimum sizes

for common
bypass and

Normal AC input

copper cables
(<100 m)

Minimum sizes

for copper load-
circuit cables

(<100 m)

Battery/terminal

connection
(<15 m)

20 kVA

10 mm

2

16 mm

2

16 mm

2

16 mm

2

16 mm

2

30 kVA

16 mm

2

16 mm

2

16 mm

2

16 mm

2

25 mm

2

40 kVA

16 mm

2

16 mm

2

16 mm

2

16 mm

2

35 mm

2

60 kVA

25 mm

2

25 mm

2

25 mm

2

25 mm

2

70 mm

2

80 kVA

50 mm

2

50 mm

2

50 mm

2

50 mm

2

95 mm

2

100 kVA

50 mm

2

70 mm

2

70 mm

2

70 mm

2

2 x 50 mm

2

120 kVA

70 mm

2

70 mm

2

70 mm

2

70 mm

2

2 x 70 mm

2

Connections are made to pre-drilled terminals.

Hole diameter: 6.5 mm (8.5 mm for 120 kVA).

Earthing cables connect to the earthing plate.
Hole diameter: 6.5 mm (8.5 mm for 120 kVA).