DoorKing 2348 Elevator Control User Manual

Page 26

Advertising
background image

DOORKING, INC., INGLEWOOD, CA 90301

Date:

Dwg. No.

Detail Wiring - 2348 Elevator Control Board

Rev.

Title:

10/11

C

M2348-065-7

1
2
3

1833,

1

835

, 1

837,

18

38

E

le

v

at

o

r Ter

m

in

als

16 VAC

PWR

INPUT

2348-010 Board 1
Floor Relays 1-16

White
Green
Black

6

9

10

1

Elevator Umbilical Cable

2

4 conductor, stranded with overall shield, 18, 20, 22 or 24 gauge is sufficient for these
connections.

3

Access Device Cable Routed with Umbilical Cable

6

Terminals 69-70, Lobby Hall Up Call.

5

Floor Relay common terminals are tied together to form a single common for floor control.

7

Ground Detect Switch must be used when Lobby Hall Up Call Relay is used.

8

Floor relays are rated for 5 amp @ 125 Volt.

4

Card
Reader

WHT
GRN
BLK

RED
WHT
GRN
BLK

1833, 1835, 1837,

1838 Controllers

or Tracker Board

Elevator
Control Panel

Elevator Car

Elevator

Control

Panel

2348-010

Access

Controller

Elevator

Car

Elevator Shaft

1

2

3

8

2

Common

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

Floor Control

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18

19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36

Not Used

Ground Detect
Switch

3

4

Floor Relays are typically set for Normally Closed (N.C.) Operation

7

11

5

5

9

11

Earth ground.

Dry Contact - no voltage applied

10

16 VAC, 40 VA UL Listed transformer

37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54

55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72

Relay 8

Relay 9

Relay 10

Relay 11

Relay 12

Relay 13

Relay 14

Relay 15

Relay 16

Relay 1

Relay 2

Relay 3

Relay 4

Relay 5

Relay 6

Relay 7

Lobby Hall Up Call

Figure 8

Page 26

2348-065-E-10-11