46-638 Magnetic Liquid Level Indicators

1.9.2.1 Mounting to an Atlas or Gemini MLI

Caution:

If equipment is used in a manner not specified by the
manufacturer, protection provided by the equipment may
be impaired.

With mounting clamps loosened, position ORS reed
switch on the MLI body so that the centerline of the stain-
less steel tube which houses the switch is at the desired
switch point level. The switch should be oriented so that
the green ground screw is closest to the top of the MLI.
See Figure 8. Tighten the clamps so that the switch is
secured to the MLI. If required, place the insulation
between the MLI body and the switch before tightening
the clamps.

1.9.2.2 Mounting to an Aurora MLI

Follow procedure for mounting to Atlas or Gemini, but
ensure that the switch is positioned on the circumference
of the Aurora body as close to the indicator as possible.

1.9.2.3 Wiring

The leads protruding from the potted end of the switch
housing are color coded as follows:

White = Common
Black = Normally Closed
Red

= Normally Open

NOTE: For supply connections, use wire with a minimum rating of

+167° F (+75° C) as required by the process conditions. Use a
minimum of 14 AWG wire for power and ground field wires.

NOTE: Housing must be grounded via protective ground screw on

upper mounting tab.

Figure 9

Wiring of ORS

Reed Switch

Contact closure shown for

both conditions of the switch

relative to the magnetic float

FLOAT ABOVE SWITCH

FLOAT BELOW SWITCH

1 (RED)

C (WHITE)

C (WHITE)

2 (BLACK)

1 (RED)

2 (BLACK)

8-32 Ground Screw

3.00

(76.2)

3.00

(76.2)

1/2"

MNPT

1.00

(25.4)

0.84

(21.3)

Figure 8

inches (mm)