Basic configuration, 1 select the control mode, 2 predefined setpoints – Aube Technologies TH144 User Manual

Page 3: 3 view the current setpoint

Advertising
background image

TH144

400-144-000-C 2008-02-08 3/6

I

2.1

Select the Control Mode

The mode indicates which system is used for temperature control.
Use the Heat / Cool button to select one of the following modes:

2.2

Predefined Setpoints

Predefined setpoints represent the temperature that you wish to have
during the day, at night or while you are away. The Comfort and
Economy setpoints are used with the Automatic mode (schedule, for
programmable models) while the Unoccupied setpoint can be used
with the Unoccupied mode (activated manually or remotely). This
table displays the default setpoints:

2.2.1 To Modify the Predefined Setpoints

NOTE:

If your thermostat controls both HEATING and COOLING, the

predefined setpoints must be configured for both applications.

NOTE:

The Cool setpoints cannot be lower than the Comfort Heat

setpoint. If this should happen, the TH144 will automatically set your
Cool setpoint 1°C (1°F) higher than your Comfort Heat setpoint.

2.3

View the Current Setpoint

To view the current setpoint, briefly press one
of these buttons

once. The arrow

indicates the setpoint.

o

Basic Configuration

2.

Programmable models only. Automatic Operating mode is
executing your schedule.

This icon is always displayed with the

or

icon which

represent the programs setpoints.

Programmable models only. Manual Operating mode. This
icon is either displayed alone (a manual setpoint was set) or

with the

or

icon

Comfort setpoint. Associated with programs 1 and 3.

Can also be used with manual mode or during a bypass.

Economy setpoint. Associated with programs 2 and 4.

Can also be used with manual mode or during a bypass.

Unoccupied setpoint. Activated from the TH144 or remotely
(REM input is connected to a remote system)

The fan runs continuously.

The heating system is ON.

The air conditioning system is ON.

Select
operating
mode

To adjust the temperature or to
view a setpoint (press once)

Time and
day settings

Schedule
programming

Comfort
setpoint

Select fan
mode

Select
control
mode

Economy
setpoint

Unoccupied
setpoint

NON PROGRAMMABLE

PROGRAMMABLE

Unoccupied mode
is activated
(yellow LED is on)

Current time
(see 1.5)

Room temperature OR
setpoint (arrow)
REM = temperature is
controlled using AC144-02
(see 1.4)

OUT = outside temperature
from the connected
AC144-02 (see 1.4)

Current control
mode (see 2.1)

See table below

Current day (see 1.5)

HEAT

Controls the heating unit(s).

COOL

Controls the cooling unit(s).

OFF

Both units (HEAT and COOL) are OFF. The fan function
is still enabled but no setpoint changes are allowed.

AUTO

Automatic changeover. Automatically alternates
between HEAT and COOL. See section 4.4 for details.

Symbol

Predefined

Setpoint

HEAT

COOL

Comfort 21°C

(70°F)

25°C

(78°F)

Economy

17°C (62°F)

28°C (82°F)

Unoccupied

10°C (50°F)

35°C (95°F)

HEAT

COOL

400-144-000-C (TH144_HVAC) ENG.fm Page 3 Friday, February 8, 2008 10:33 AM

Advertising