TH114

400-114-000-B 21/2/05 2/2

7.1 Backlight

When either of the

buttons is pressed, the display is lit for 10

seconds. The setpoint appears for 5 seconds, then the actual tem-
perature is displayed.

When the backlight button is pressed, the display is lit for 5 sec-
onds. NOTE: If the thermostat is mounted on a GFCI-equipped
power base, this button is used for the GFCI test.

7.2 Displaying and Setting the Temperature

The thermostat normally displays the actual temperature. To view
the setpoint, press once on one of the

buttons. The setpoint is

displayed for 5 seconds. During the setpoint display, press one of
the

buttons to change it. To scroll the setpoint faster, press

and hold the button.

7.3 Setting the Floor Temperature Limits (AF model only)

The thermostat generally turns heating On or Off to con-
trol the ambient temperature. However, if the floor tem-
perature drops below the set minimum floor temperature
limit or rises above the maximum limit, the thermostat
will turn heating On or Off respectively, regardless of the
ambient temperature, to maintain the floor temperature
within the desired limits.

The minimum and maximum floor temperature limits are
factory-set at 10°C (50°F) and 28°C (82°F) respectively. To modify
the limits, proceed as follows:

n

Switch the thermostat to Standby.

o

While pressing any button, switch the thermostat back to On to
access the floor temperature limit settings.

p

Press the Test button briefly to switch between minimum and
maximum floor temperature settings.

q

Press the

buttons to set the desired limit.

r

Press the Test button for 3 seconds to save your modifications.
After the data are saved, the thermostat displays the actual
ambient temperature or “– –”.

Note

: Your modifications are also saved if no button is pressed for

60 seconds.

s

Switch the thermostat to Standby and back to On to reset the
GFCI and return to the normal display.

:

Power supply: Refer to the power base installation instructions.

Ambient setpoint range (A/AF models): 5°C to 30°C (40°F - 86°F)

Floor limit range (AF model): 5°C to 40°C (40°F - 104°F)

Floor setpoint range (F model): 5°C to 40°C (40°F - 104°F)

Setpoint resolution: ± 0.5°C (1.0°F)

Display resolution: ± 0.5°C (1.0°F)

Duty cycle: Refer to the power base installation instructions.

Storage: -20°C to 50°C (-4°F - 120°F)

AUBE TECHNOLOGIES INC. ONE (1) YEAR LIMITED WARRANTY

This product is guaranteed against workmanship defects for a one
year period following the initial date of purchase. During this period,
AUBE Technologies Inc. will repair or replace, at our option and
without charge, any defective product which has been used under
normal conditions.

The warranty does not cover delivery costs and does not apply to
products poorly installed or randomly damaged following installa-
tion. This warranty cancels and replaces any other manufacturer's
express or implied warranty as well as any other company commit-
ment.

AUBE Technologies Inc. cannot be held liable for related or random
damages following the installation of this product. The defective
product as well as the purchase invoice must be returned to the
place of purchase or mailed, prepaid and insured, to the following
address.

7. Operation

8. Technical Specifications

9. Warranty

1 0. Service

705 Montrichard
Saint-Jean-sur-Richelieu, Quebec
J2X 5K8
Canada

T: (450) 358-4600
1-800-831-AUBE (2823)
F: (450) 358-4650
[email protected]

For more information on our products, visit us at:

www.aubetech.com

Advertising