The Blow-Off Valve — There are two

blow off valves on the boiler: The

main valve at the rear of the boiler

and the water gauge glass blow off

valve. The boiler blow off valve sup-

plied with the boiler should be

screwed to the blow off pipe at the

rear of the boiler and connected to a

blow off receptacle of approved

design. This should be done in accor-

dance with state and local codes.

The Feed Water Piping
1)
Provisions must be made for ade-

quate water supply and properly

sized piping. Piping must be done in

compliance with all local codes. The

following chart may be used as a

guideline for sizing.

BHP

Minimum Water

Supply Piping Size

Inches

Millimeters

6

1/2

12.5

9.5

1/2

12.5

10

1/2

12.5

15

3/4

19

20

3/4

19

30

1

25

40

1

25

50

1

25

60

1

25


2)
When feeding the boiler using a

return system, the city water pressure

should not exceed 40 PSI. A pres-

sure reducing valve should be

installed a head of the return tank

when above this pressure.
3) It is important that all piping be

lined up and not forced into place. It

is recommended that you begin pip-

ing at the pump. If the lines are

ended at the pump, particularly if the

last piece is cut too short or long, the

pump will be forced to meet the pipe

and strain or distortion will result.

4) Do not use the pump as a piping

support. It is critical that the pipe be

independently supported near the

pump so no strain will be transmit-

ted to the unit.
5) Connect the feed water stop

valve to the feed water pipe at the

rear of the boiler and pipe it to the

return system.

The Water Column
Install the piping from the water

column and water gauge glass to a

safe blow-off point.

Description/Instructions

35-G 1/01

4

1/2

12.5