SVX Series – Survive-All Exit Sign

SVX Series – Survive-All Exit Sign

AC/DC & Self-Powered Models

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should
always be followed including the following:

READ AND FOLLOW ALL SAFETY
INSTRUCTIONS

1. Do not let power supply cords touch hot surfaces.

2. Do not mount near gas or electric heaters.
3. Use caution when handling batteries. Avoid possible shorting.
4. Equipment should be mounted in locations and at heights where it

will not readily be subjected to tampering by unauthorized personnel.

5. The use of accessory equipment not recommended by the manufac-

turer may cause an unsafe condition.

6. Do not use this equipment for other than intended use.
7. All servicing should be performed by qualified service personnel.

SAVE THESE INSTRUCTIONS

Installation Instructions

1. Turn off unswitched AC power.

Canopy Mount

a. Remove canopy assembly from carton. Remove mounting plate

from canopy and retain securement screw.

b. Route unswitched AC circuit wires into the junction box and leave

6” of wire length.

c. Remove proper knockouts in canopy backplate for desired

mounting position.
For Nexus option, install the liquid tight fitting, provided with the
unit. For Ceiling mount, use the k’out located on side of the unit
(opposite side of the diagnostic display). For Side mount, use the
k’out located on top of the unit (see fig. 4).

d. Feed unswitched AC wires through large hole in canopy mount-

ing plate.

e. Make sure the securement screw is accessible (see fig.1 part #

13). Use existing screws in junction box to secure canopy back-
plate to the junction box.

f. Remove lens, exit panel and diffuser panel on the front of the unit

(use the supplied bit to remove the tamper-proof screws).

g. In order to access the knockouts of the frame, remove the 4 elec-

tronic module screw(s) holding the electronic module to the frame
and separate them (see fig.2).

Figure 1

Part List

1. Tamper-proof screws short

(4 per lens)

2. Tamper-proof screws long

(2 per lens)

3. Lens
4. EXIT panel
5. Diffuser panel
6. Frame
7. Electronic module
8. Electronic module screws

(4)

9. Backplate (single face sign)
10. Backplate tamper-proof

screws (4)

11. Lock-nuts (2)
12. Gasket washer (2)
13. Canopy securement screw
14. Canopy
15. Nipple assembly (2)
16. Canopy backplate
17. Junction box screws (not

supplied)

18. Junction box (not supplied)
19. Nylon washer (2 for wall

mount)

20. Junction box gasket (for

wall mount)

Figure 2