Ii 2 g d, Eexd system drawing, Equipment markings – Fire Fighting Enterprises Talentum UV/IR2 Flame Detector User Manual

Page 3: Atex

Advertising
background image

10

EExd System Drawing







Hazardous Area

Safe Area

Safe Area Apparatus


Unspecified except that it
must not be supplied from
nor contain under normal or
abnormal conditions a source
of potential exceeding 250V
RMS or 250V DC with
respect to earth.

-

+

24V DC Normal

(Break supply to reset

if detector set to latch)

Zone

Refer to note 6

Fault
Relay

Fire
Relay

2

1

-

+

Flame Detector

6

5

7
8

Fault
Relay

Fire
Relay

2

1

-

+

Flame Detector

6

5

7
8

EO

L

No

Barriers

Required

+

-

-

+

+

-

i

= See detector data

sheet for details

NOTE 1
WARNING – Ensure ALL power is OFF before/during
installation/maintenance.

NOTE 2
Ensure the details on the enclosure label comply with
the hazardous area specified.

NOTE 3
The installation must comply with national installation
requirements (for example to EN 60079-14)

i

24V DC Normal

(Break supply to reset

if detector set to latch)

2

1

-

+

Flame Detector

No

Barrier

Required

+

-

-

+

NOTE 4
If required a loading resistor or end of line device (EOL)
can be connected between the detector terminals of any
circuit. The total power dissipation and temperature
classes within the enclosure must not be exceeded,
30W – T6.

3


Equipment Markings


ATEX

(EU Directive 94/9/EC)




II 2 G D













Equipment



Definition

Type of Explosive

Atmosphere

Group II

Category

G -

gas vapour mist

D

- dust

Zone

1

- very high level of protection

in which explosive atmosphere mixtures of air gases,
vapours or mist are present continuously, for long
periods

0

2

- high level of protection

in which explosive atmosphere mixture of air and gases,
vapours or mist are likely to occur

1

3

- normal level of protection

in which explosive atmosphere mixtures of air and
gases, vapours or mist are unlikely to occur and if it
occurs it will exist only for a short period

2

These Flame Detectors are suitable for equipment categories 2 and 3, G or D.

Note: The detectors are not certified for category 1 areas, see ‘IS’ products.


Table 1 Equipment Categories and Type of Explosive Atmosphere (Group II)

CE Marking

EU Explosive
Atmosphere
Symbol

Group II