Humidifi er, De-humidifi er, Fresh air – LOCKSTATE LS-90 Installation Guide User Manual

Page 7: Wire reference chart

Advertising
background image

12

PG

12

Humidifi er -

To use the

/6 internal humidistat to control an external

humidifi er unit, connect it as shown. Connect the H
terminal to the control leg of the humidifi er relay. This
allows H to turn the humidifi er ON and Off.

De-Humidifi er -

To use the

/6 internal humidistat to control an external

De-humidifi er unit, connect it as shown. Connect the DH
terminal to the control leg of the dehumidifi er relay. This
allows DH to turn the dehumidifi er ON and Off.

Fresh Air -

The Fresh Air feature uses the EX relay to control a baffl e
on a fresh external air source. Connect the 24VAC baffl e
to C and EX terminals.

BAFFLE

RH

FOR FRESH AIR BAFFLE

EX

R

C

/6

FURNACE
POWER

H or DH

To HUMIDIFIER
or
DEHUMIDIFIER

RELAY

RH

USING 24VAC ADAPTER

H or DH

R
C

/60

FURNACE
POWER

AC

ADPT

FOR EXTERNAL HUMIDIFIER
or DEHUMIDIFIER USING

H or DH

To HUMIDIFIER
or
DEHUMIDIFIER

RELAY

RH

FOR EXTERNAL HUMIDIFIER
or DEHUMIDIFIER USING
HVAC SYSTEM's 24

VAC

H or DH

R
C

/60

FURNACE
POWE R
24VAC

13

PG

13

WIRE REFERENCE CHART

Your Wires

LS-90 Terminal

R or V or VR

RH and RC Single power for HEAT and COOL

RH or 4

RH Power for HEAT (RH not connected to RC jumper clip removed)

RC

RC Power for COOL (RH not connected to RC jumper clip removed )

W

W Heat control

W2

W2 2nd stage HEAT or heat pump auxiliary heat

W3

W3 3rd stage HEAT or 2nd stage of 2 stage auxiliary heat

?

A 3rd wire for zoned hot water heat (see zoned systems pg14)

Y

Y COOL control or 1st stage compression for heat pump.

Y2

Y2 2nd stage COOL control or 2nd stage compression for a heat pump

G or F

G FAN control

C or X

C Common 24VAC power (to power thermostat ) NOTE: TRANE uses B for this connection

E

n/a Emergency heat (do not connect, tape off)

L

n/a System monitor (do not connect, tape off)

T

n/a Outdoor sensor (do not connect, tape off)

H

External

Humidifi er

DH

External

De-Humidifi er

EX

External fresh air baffl e

B or

B Heat pump changeover (cool to heat, powered in heat)

O

O Heat pump changeover (heat to cool, powered in cool)

B and O

IMPORTANT: If there are both B and O wires (Trane pump

products) DO NOT CONNECT B to B terminal, connect B to C

terminal. If not a Trane product tape off B.

Lennox Heat Pump
V or VR or R

RH Power for HEAT

M or Y

Y

Y or W or W2

W2

F or G

G

R or O

OX or X2 or C

C

Trane Products [American Standard]
B

C

W or W1 or X2

W2