THEA 92 Specifications

Input

Output

System Protection

Safety and EMI/EMC

Environmental

Control Interface

Rated Input Voltage

120 to 277 Vac

Rated Input Frequency

50/60 Hz

Power Factor EN61000-3-2

@120 Vac 0.99 W/VA; @277 Vac 0.91 W/VA, 100% load typical

Input Current Total Harmonic Distortion @120 or 277 Vac 13% typical, 100% load

Rated Output Power

92 W max

Efficiency

Full load @120 Vac (no load on auxiliary output); 88% typical

System Power Cycle Delay

0.9 second typical

Output Current Tolerance

+/-5 % of nominal

Auxiliary Voltage

12 Vdc @ 160 mA, less than 1% load/line regulation

Output

Over voltage, over current, short circuit protection

Over Temperature

Power supply will throttle back output current gradually when case
temperature reaches 85°C/185°F nominal.

Agency Approvals

UL 8750 NEC Class 2 outputs, US only

Emissions

ICES-003; FCC Title 47, Part 15, EN55022 Class A

EN61000-3-2

Harmonics Emissions, Class C

EN61000-4-4

Electrical Fast Transient, 1KV Criteria B

EN61000-4-5

Surge, 2KV Criteria B

EN61000-4-11

Voltage Dips, Interruptions, and Voltage Variations, according to
EN61547 and EN55024

Location Rating

Dry/Damp Location

Operating Ambient Temperature

-20°C to 50°C / -4°F to 122°F

Maximum Case Temperature

T

c

=80°C / 176°F

Storage Ambient Temperature

-40°C to 80°C/ -40°F to 176°F

Relative Humidity

5% to 95% noncondensing

Mean Time Between Failure
(MIL HDBK-217F)

>125,000 hours @ T case 70°C/158°F

Control Method

Analog 0-10 Vdc, IEC 60929 Annex E Outputs 0.5 mA max or variable
0-10 Vdc Voltage Source; Class 2 outputs.

Loss of Analog Input Signal

Outputs will go to 100% light intensity in less than 1 second