Recycling thermostat, Replace cover on thermostat – Robertshaw 9700i INSTALLATION User Manual

Page 2

Advertising
background image

Connect wiring between unit and
heat pump. For 9700i (single stage
heat pump applications):
Wire as shown and move jumper J1
to the HP position (top two pins).

7

Connect wiring between the thermo-
stat and the indoor sensor (9020i)
and the outdoor sensor (9025i), if
used. Use twisted pair wiring
(22AWG minimum) with a maximum
length of 300 feet (or 100m).

8

Proceed with programming per
instructions on the display or in the
user’s manual.

11

Replace cover on thermostat.

9

Set Your Name
To set your name and phone
number into the thermostat press
MENU, select INSTALLER
SETTINGS, and CONTACT
INFORMATION The screen at the
bottom left should appear.

To enter your name press EDIT.
Use the UP or DOWN button to
scroll through the characters.
(DOWN gets you to the letters
faster.) After each letter press NEXT.

When you are done entering your
name, press ACCEPT.

Insert 4 AA alkaline batteries. Make
sure to follow proper polarity.

10

Controls Americas
515 South Promenade Avenue
Corona, CA 92879-1736
United States of America
Made in Mexico
www.about-i-series.com

111-304C

12

CONTACT INFORMATION

BACK

EDIT

ACCEPT

NEXT

CONTACT INFORMATION

AIR EXPERTS

CONTACT INFORMATION

AIR EXPERTS

ACCEPT

NEXT

1

ACCEPT

NEXT

CONTACT INFORMATION

AIR EXPERTS

1-555-555-1212

Recycling Thermostat

If this thermostat REPLACES a thermostat that contains mercury,
DO NOT discard the old thermostat in the regular trash. Mercury
is harmful to humans and the environment. For this reason, do
not open, break, or crush the mercury cell. If mercury leaks from
a damaged cell, DO NOT touch or handle mercury with bare
hands. Use protective, non-absorbent gloves to place mercury
into a sealable container. Fill the container with sand or another
absorbent material and seal the container completely.

Return the mercury or mercury products, in a sealed container, to
Invensys Climate Controls or a local recycling center for proper
disposal. If you have any questions, call Robertshaw technical
support at 1-800-445-8299.

Invensys Climate Controls
28C Leigh Fisher Blvd.
El Paso, TX 79906
Attn: Mercury Recycling Center

Set Your Phone Number

Now enter your phone number.
Use the UP and DOWN arrow to
select the first number. Press NEXT.
When you have completed entering
your phone number, press ACCEPT.

The screen will return to the
INSTALLER SETTINGS. Finish
setting the thermostat for the
application.

13

Rc

W

Y

Rh

O

B

G

G

Y
R

O

Thermostat

Rh - 24VAC
Rc - 24VAC
W -

Not used

O - Reversing valve (cool)
B - Reversing valve (heat)
G -

Fan

Y - 1st stage heating/cooling

TERMINAL DESIGNATIONS

9700

i

Equipment wiring
terminals.
Please refer to
heat pump installation
manual for
proper connections.

HP

J1

FN

Factory installed jumper