Operating manual, Troubleshooting guide, Cooltech – Robinair 15120A_15121A User Manual

Page 5: Specifications, When you need help

Advertising
background image

Operating Manual

4

3. When the flow of oil has stopped, tilt the

pump forward to drain residual oil.

4. Replace the OIL DRAIN cap. Remove the

exhaust filter, and fill the reservoir with

new vacuum pump oil until the oil just

shows at the bottom of the sight glass. The

approximate oil capacity of the pump is 488

milliliters (16

1

/

2

ounces).

5. Verify the inlet ports are capped, then turn

ON the pump. Allow it to run for one minute,

then check the oil level. If the oil is below the

sight glass OIL LEVEL line, add oil slowly

(with the pump running) until the oil reaches

the OIL LEVEL line. Replace the exhaust

filter (hand tight), making sure the inlet is

capped and the drain cap is tight.

6. If the oil is badly contaminated with the

sludge that forms when water is allowed to

collect in the oil, you may need to remove

the oil reservoir cover and wipe it out.

Repeat this procedure as required until the

contami nation is removed. Replace the OIL

DRAIN cap, and refill the reservoir to the correct

level with fresh pump oil (see Step 4).
Cleaning the pump
Clean the pump with soap and water only.

CAUTION: Do not use commercial cleaners

that contain degreasing agents that can

damage polycarbonates. The pump handle and

base are made of Lexan*, one of the toughest

polycarbonate plastics available. However, it is

sensitive to degreasing agents.
*Lexan is a registered trademark of General

Electric
Motor lubrication
After three years of normal service or one year of

heavy-duty service, add electric motor oil or SAE

10 oil.

Troubleshooting guide

Your CoolTech pump has been designed for

dependable use and long life. If something

should go wrong, however, the following guide

will help you get the pump back into service as

quickly as possible.
If disassembly of the pump is required, please

check your warranty. The warranty may be

voided by misuse, or customer tampering which

results in the pump being inoperable.
Failure to start
Check the line voltage. Robinair pumps are

designed to start at +10% line voltage at 0

o

C

(32

o

F). At extremes, however, switching between

the start and run windings may occur.

Oil leakage
1. Confirm the oil is not a residual accumulation

from spillage, etc.

2. The module cover gasket or shaft seal may

need replacing. Follow instructions in Seal

Replacement Kit No. 15367.

If leakage exists in the area of the oil drain

plug, reseal the plug using a commercial pipe

thread sealer.

Failure to pull a good vacuum
1. Confirm the Iso-Valve is OPEN.
2. Are the vacuum gauge and all connections

in good conditon and leak-free? Confirm

leakage by monitoring vacuum with a

thermistor gauge while applying vacuum

pump oil at connections or suspected leak

points. Vacuum will improve briefly while the

oil is sealing the leak.

3. Is the pump oil clean? A badly contami nated

pump may require several oil flushes. See

Oil Change Procedure. Note: Use only high

vacuum pump oil such as Robinair’s Premium

High Vacuum Pump Oil. Other oils will

prevent pull-down to a deep vacuum.

4. Confirm the gas ballast knob is tightly closed.
5. Is the oil is at the correct level? For maximum

pump operation, the oil must be even with the

OIL LEVEL line on the sight glass when the

pump is running. Do not overfill. To check oil

level, start the pump with the inlet capped.

Add oil if necessary.

CoolTech

®

specifications

Model 15120A

Frequency Range ..........................................60 Hz

Voltage Range ................................................ 115V

Free Air Displacement .................. 283 l/m (10 cfm)

Stages .................................................................. 2

Motor Speed ............................................ 1725 rpm

Factory Micron Rating ...........................15 microns

Approximate Oil Capacity ............488 ml (16

1

/

2

oz.)

Weight .........................................17.24 kg (38 lbs.)

Width ............................................. 14.29 cm (5

5

/

8

")

Height ............................................ 27.3 cm (10

3

/

4

")

Length............................................ 41,9 cm (16

1

/

2

")

Intake .............................

1

/

4

",

3

/

8

", and

1

/

2

" SAE MFL

Min. Starting Temp. (at 90% Voltage) .... 0

o

C (32

o

F)

Motor Size ...........................

1

/

2

HP, Capacitor Start

Operating Temp. ................................ 74

o

C (165

o

F)

When you need help

If these procedures do not correct the problem,

contact your nearest Robinair distributor. The

distributor may recommend an additional

replacement part (this manual contains a parts

list) or suggest you send your pump to the nearest

authorized service center.