Rev 1.0 Series X11CA Hardware Manual

3. Event Sequences

Hardware Control-© 2002 Ronan Engineering

32

3.4.2 F1A-1

First Out with Automatic Reset

The First Alarm operates as a basic sequence A. Subsequent alarms operate as a
status lamp. The visual display of the subsequent alarms is steady on until the
events return to normal, at which time the lamplights go off.

Key applications:

1. If First out is the only alarm of importance.
2. Current status of the subsequences is of interest.
3. Minimum operator action is preferred for the subsequent alarms.
4. Subsequent alarms must lock-in and be annunciated by audible and

visual flashing, see sequence F3A.