Chassis:

Up to 100 I/O Modules*

Power Supply Filter Module

AUX Relay Modules

Communications Module

System Size:

Basic Cabinet Module is 3.50 in.

(88.90mm) x 3.50 in. (88.90mm)

Enclosures:

Weather Proof

- NEMA 4 (optional)

- NEMA 4X (optional)

- NEMA 12 (optional)

Panel Mount

Surface-Mount

19” Rack-Mount

*Multiple chassis can be connected to share communications

capabilities up to a maximum of 100 Modules.

FEATURES

Alarm Display LEDs:

Minimum of 4 LEDs per window

Colors: Red, Green, Yellow, White

and Blue

Dual Redundancy:

(-1000 & -2000 Models Only)

Built-In Diagnostics:

Hardware startup

Periodic Maintenance

PUSHBUTTON INPUTS

Front Bezel Pushbuttons

Rear Input Terminals

via Network Interface

- Silence

- Acknowldge

- Reset

- First-Out Reset

- LED Test

Lamps, Logic:

24Vdc

Field Contacts:

Vdc: 24, 48, or 125 Vdc

Vac: 115, 240 Vac

X11-2048 INTERFACE MODULE

Communications with the SER/HMI or

a Host via a 10/100 BaseT Interface via:

Ronan Proprietary Protocol

ModBus RTU Protocol

DNP 3.0 Protocol via Ronan REC-UCM

(Optional)

Alarm module monitoring generates

system error with missing module.

Continuous alarm module configuration

monitoring. (Verifies each alarm module

for correct configuration and reconfigures

improperly configured modules)

Facilitates and preserves

Alarm Module configuration

X11-2047 ALARM MODULE

(4) Opto-Isolated Channels

per module featuring:

Output Response 1 to 16383mS

H/W First-Out Discrimination 1mS

S/W First-Out Discrimination <100mS

ENVIRONMENT

Operating Temperature

- 0 to 60º C (32 to 140ºF)**

Storage Temperature

- 40 to +85ºC (-40 to +185ºF)

Humidity 0-95% RH, non condensing

** Operating at temperatures over 50ºC for more than a few

hours at a time will shorten the life of the system. The average

temperature over life of the system should be <50ºC, but

never exceeding 60ºC

WARRANTY

Ronan warrants equipment of its own manufacture to be free

from defects in workmanship and material under normal

conditions of use and service, and will replace any component

found to be defective, on its return, transportation charges

prepaid, within one (1) year of its original purchase. This warranty

carries no liability, either expressed or implied, beyond our

obligations to replace the unit which carries the warranty.

Extended Warranties are available.

28209 Avenue Stanford, Valencia, CA 91355 U.S.A. • 800-327-6626 • Fax 661-295-6063

http://www.ronan.com E-Mail: [email protected]

DISPLAY PRODUCTS DIVISION

TECHNICAL SPECIFICATIONS

SYSTEM CONFIGURATIONS

Fully Configurable Using the

Ronan Configuration Tool

(software provided):

Event Time Stamping to 1mS

resolution with Date and Time of Day

correlation when an external IRIG-B

Timing Source is provided
Stores latest 1000 events in

distributed, non-volatile memory

Compatible with the Ronan’s

X1001 SER/HMI, X110 and X118

Remote Alarm Annunciators

SYSTEM VOLTAGE

1500V Isolation to Ground and

Channel-to-Channel

Vdc: 24V, 48V or 125V Vac: 115V or 240V

(Selectable by Module)

Wetted or Dry Contacts

(Selectable by Module)

Normally Open/Normaly Closed

Contact Sensing

(Field Selectable Configurable by Channel)

Input Response Time < 1mS

Multiple Filter Options

(S/W Configurable by Channel)

Hot swapable (remove and replace

module without disrupting system

operation)

Field contact Debounce filter with:

- Filters for each field contacts normal and

alarm transition

- Integrating and non integrating filter types

- Units in miliseconds, seconds, and minutes

Via TCP/IP over a network (LAN)

Advertising