Ronan X120 User Manual

Page 4

Advertising
background image

Page 1 of 12

SPECIFICATIONS - MODEL X120 MULTIPLEXER/TERMINATION UNIT

Features

Monitors up to 48 switching devices

Reliable high-speed event transmission

Interfaces with most plant computers and the Ronan Model X110 Serial Input Visual Annunciator

Internal relay for self-test and power supply status

Digital filtering to assure accurate monitoring of status changes

Up to 32 units may be series connected to monitor up to 1,536 total inputs

Considerable savings in cable costs by the use of serial transmission

General Description
The Ronan Model X120 Multiplexer/Termination Unit is designed to continuously monitor up to 48 field contacts and/or
solid state switching devices. Any input status change is converted to serial data which can be transferred to a plant computer
or serial input display device, like Ronan’s Model X110 visual annunciator. The input signals are monitored using opto-
isolated input circuits to provide isolation between input signal voltages and the Model X120 logic circuits. The 48 inputs are
sequentially scanned on a continuous basis.

Input status changes are digitally filtered for a 16 millisecond period before being transmitted over the high speed serial line.
Self-test and watchdog timer circuits, in addition to power supply monitor circuits, are displayed by means of LED indicators.
Loss of a power supply voltage will de-energize the self-test relay.

Up to 32 Model X120 units can be daisy-chained to form a single serial output which monitors the status of up to 1,536 field
contacts or solid state switching devices.

Each Model X120 unit receives 5 VDC power to operate its internal logic. An isolated 125 VDC or 24 VDC voltage source
can be used to power the field contacts. The isolated power source, along with digital filtering, assures maximum noise
immunity for system operation.

Specifications
Input Voltage:
X120 Logic: 5 VDC, 24 VDC, 48 VDC, 115 VAC, 125 VDC or 230 VAC

±

10%

Isolated Field Contact: 24 or 125 VDC

±

20%

Power Requirements:

Isolated: 0.5 A @ 24 VDC plus 0.25 A @ 24 or 125 VDC
Non-isolated: 0.75 A @ 24 VDC

Capacity: 48 inputs

Protocol: Ronan Proprietary

Data Transmission:

Type

Distance (Feet)

Rate (Baud)

RS422/485

4000

2400

4000

4800

4000

9600

2000

19200

Universal Data Format: per point status change

# Symbol:

Start of data string

2 Digits:Termination assembly ID
2 Digits:Point ID
1 Character:

O=Open, C=Closed, F=False Alarm (ignore message)

ODH Character: End of data string

Ronan Proprietary Data Format: Contact Factory