Ronan X54-3224 User Manual

Ronan Equipment

Advertising
background image

Page 1 of 2

Rev. 0

A Family of

Products!!!

Transmitters

Alarm Trips

I/I Isolators

Ronan Engineering Company

Ph: 800-327-6626 Fax: 818-992-6435 E-mail: [email protected] Web: www.ronan.com

High Density Four (4) Channel Packaging

Input Loop Powered

Low Input Loop Burden (<6 vdc @ 250 ohm load)

Ideal for High Density I-to-I Isolator Requirements

Max. Output Loop Load = 500 ohms

Full Input/Output/Power and Channel Isolation

Standard 35 mm DIN Rail Mounting

DESCRIPTION:

The X54-3224 is a four channel current-to-

current repeater/isolator transmitter powered by the input 4-20 mA cur-
rent loops. Features include: two piece plug-in connectors for easy wir-
ing and maintenance; full 1000 vac isolation; and front panel access to
ZERO and SPAN Adjustments. Dual output options per channel al-
lows for matching load requirements and Input loop burden. RFI pro-
tection, wide operating temperature, and high accuracy are standard
features.

4-20 mA Signal Repeater/Isolator Transmitters - DIN Rail Mounting

X54-3224

Four (4) Channel Input Loop Powered I to I Isolator (mA transmitter)

ISO 9001

REGISTERED

SPECIFICATIONS:

Inputs:

4-20 mA (input loop burden is <6 vdc drop+(IloadXRload))

Outputs:

Output #1 = 4-20 mA into 0 to 99 ohm load (3 vdc)
Output #2 = 4-20 mA into 100 to 500 ohm load (10 vdc)

Span Adjustment:

Front-accessible, multi-turn, infinite resolution potentiometer
permits minimum +/- 5% adjustment.

Zero Adjustment:

Front-accessible, multi-turn, infinite resolution potentiometer
permits minimum +/- 5% adjustment

Calibrated Accuracy: +/- 0.1% of span
Isolation: 1,000 vac between channels, input and output.
Common Mode Rejection: > 120 dB, DC at 60 Hz.
Common Mode Voltage:
1000 volts peak AC maximum without damage.
Ambient Temperature Coefficient:
Ambient temperature range: 32 to 158 F (0 to 70 C).
Gain: < +/- 0.01 %/ F.
Zero: < +/- 0.005 %/ F.

Ambient Temperature Range:
Operating: -20 to 158 F (-25 to 70 C).
Storage: -40 to 158 F ( -40 to 70 C).
Radio Frequency Effects:

< 0.4 mV (referred to input) + 0.2% of span (referred to out-
put) when exposed to 5W transmitter with frequency range
20-460 MHz at a distance of meter.

Terminals:

High temperature polyester type, wire size 12 AWG max., 10
A max., 300 V max.

Specifications apply at 23 +/- 2°C (74 +/- 2°F) unless otherwise specified, and are subject to change without notice,

Advertising